1.  DESCRIPTION
The  BA648CF-F  fieldbus  indicator  is  a  general
purpose  FOUNDATION™  fieldbus  instrument  that
may  be  configured  as  a  fieldbus  node  or  as  a
fieldbus listener.  It can display up to eight fieldbus
process  variables  on  a  five  digit  LCD  and  31
segment  analogue  bargraph.      The  instrument  is
bus  powered  so  no  additional  power  supply  is
required.

As  a  fieldbus  node  the  indicator  is  configured  via
the fieldbus host.

             Communication             Fieldbus Function
                 Protocol                             Blocks

FOUNDATION™ fieldbus 

Input Selector (2 x IS)

                                  

Digital input     (6 x DI)

Device  Description  files  may  be  downloaded  from
the  Fieldbus  Foundation  or  from  the  BEKA
associates websites.

When  configured  as  a  fieldbus  listener  the
BA648CF-F  is  not  visible  to  the  fieldbus  host  and
can  only  be  configured  using  the  push  buttons  on
the front of the instrument.

Housed  in  a  robust  72  x  144  panel  mounting  DIN
enclosure, the BA648CF-F has an IP66 front panel
and  is  supplied  with  a  gasket  to  seal  the  joint
between the instrument and the panel.

The instrument’s communication protocol is shown
on the rear  of the instrument.  The ‘-F’ order code
suffix  also  indicates  the  protocol  but  is  not  shown
on  the  instrument  idendification  label.  There  is  an
alternative  version  of  the  fieldbus  display,  order
code  BA648CF-P  for  use  on  PROFIBUS  PA
networks.

2.  OPERATION
The  BA648CF-F  fieldbus  indicator  can  display  up
to  eight  pre-configured  FOUNDATION™  fieldbus
process  variables  designated  in-1  to  in-8.      The
operator  can  select  which  variable  is  displayed
using  the 

and 

  push  buttons  which  scroll  the

display  through  the  eight  inputs.      A  numeric
annunciator  on  the  left  hand  side  of  the  display
shows  which  of  the  eight  inputs  is  currently  being
displayed.

2.1  Error messages
When  the  BA648CF-F  is  configured  as  a  listener
the following error messages may be displayed:

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  SYSTEM DESIGN
The  BA648CF-F  FOUNDATION™  fieldbus  indi-
cator  is  powered  via  the  fieldbus  which  is
connected  to  non-polarised  terminals  1  and  2  as
shown in Fig 1.  The indicator may be connected to
any  FOUNDATION™  fieldbus  segment  that  can
supply an additional 13mA at between 9 and 32V.

Fig 1  Typical FOUNDATION™ Fieldbus

M  

segment

Summary of Contents for BA648CF-F

Page 1: ...Issue 3 23 rd June 2011 BA648CF F FOUNDATION fieldbus Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...ss display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5...

Page 3: ...protocol is shown on the rear of the instrument The F order code suffix also indicates the protocol but is not shown on the instrument idendification label There is an alternative version of the fiel...

Page 4: ...r panel mounting clips Fig 2 BA648CF F dimensions 4 2 Installation Procedure a Insert the BA648CF F into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA648CF F may be reset to the factory defaults that are...

Page 6: ...the P button causes the BA648CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 7: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 8: ...8...

Page 9: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 10: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 11: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 12: ...bargraph Bargraph configuration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed...

Page 13: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 7 2 Tag number The BA648CF F c...

Reviews: