background image

17

Step 3  Turn square root extractor off

With 'root' displayed, press P  which will
reveal the root extractor status.  The root
extractor can be turned on or off by
operating the Up or Down buttons.  Select
'OFF', and press E to return to the 'root'
prompt in the main menu.

Step 4 Select frequency of maximum mains

(line) rejection

Scroll though the main menu until 'Cond' is
displayed; press P which will result in the
instrument displaying '0000' with the most
significant digit flashing.   To prevent
accidental adjustment the Cond sub-menu
is protected by the code word 'SurE'' which
must be entered character by character
using the Up and Down buttons plus  P  to
move control to the next digit. Note: S is
entered as 5.  When 'SurE' has been
entered pressing E   will result in the 'FrE'
prompt.  Press P to enter the function and
using the Up or Down buttons select '50'.
Finally, press E twice to return to the
'Cond' prompt in the main menu.

Step 5  Define function of 

P

 push-button

 Select

'C--P' from the main menu and press P to
reveal the function of the P push-button in
the operating mode.  Select percentage
'PC' and return to the main menu by
pressing  E.

Step 6 

Define rate display resolution

Select 'rESn' from the main menu and
press  P to reveal the current resolution of
the rate display.  Using the Up  and  Down
push-buttons select a resolution of '1' and
return to the 'rESn' prompt in the main
menu by  pressing  E.

Step 7 

Position rate & total decimal points

Select 'd.P.' from the main menu and press
P.  The rate and total displays will be
activated with one digit of the total display
flashing.  Press the Up or Down push-
button until the second least significant
digit and following decimal point of the total
display flash.  This gives the required total
display resolution of 0.1

Press P to move control to the rate display.
Using the Up or Down  push-button move
the flashing digit to the least significant
position (right hand side) which will result
in no decimal point in the rate display.

Finally press E to return to the 'd.P’.
prompt in the main menu.

Step 8  Calibrate the rate display

Scroll through the main menu until 'CAL' is
displayed.  Press and the instrument will
request a 4mA input by displaying  'ZErO'.
Set the input current to 4.0000mA and
press P again which will reveal the existing
rate display.  Using the Up,  Down and  P
push-buttons enter the required zero
display of  0000   Press E to enter this
calibration figure.  The instrument will
display ‘Ent’ for a few seconds before
returning to the  'ZErO' prompt.

Press the Up push-button  and the
instrument will request a 20mA input by
displaying  'SPAn'.  Set the input current to
20.0000mA and again press P which will
reveal the existing rate display at 20mA.
Using the Up,  Down and P push-buttons
enter the required display of  1100  Press
E to enter this calibration figure. The
instrument will display ‘Ent’ for a few
seconds before returning to the  'SPAn'
prompt.

Finally press E again to return to the 'CAL'
prompt in the main menu.

Step 9  Define the timebase

In this example the rate display represents
flow per minute so it is necessary to set the
instrument timebase to 60.  This will divide
the rate display by 60 to provide the
correct total display.

Select ‘t-bASE’ from the main menu and
press  P to reveal the current setting.
Using the Up or Down  button select ‘tb –
60’ and press E to return to the main
menu.

Summary of Contents for BA558C

Page 1: ...Issue 3 1st October 2010 BA558C 4 20mA loop powered panel mounting rate totaliser issue 3 Label Rate display Annunciators for optional alarms Rotating flow indicator Total display...

Page 2: ...factor 5 14 Percentage clip off 5 15 Local reset of total display 5 16 Security code 5 17 Over and under range 6 Calibration Examples 6 1 Using an external current source 6 2 Using the internal refer...

Page 3: ...applied to the instrument initialisation is performed After a short delay the following display sequence occurs All segments of the display are activated for about 3 seconds Decimal points on large d...

Page 4: ...ators plus a flow indicator as shown on page 1 Rate Shows the flow rate on the smaller display five digit display Total Shows total flow since the display instrument was last reset on the larger eight...

Page 5: ...instrument provides IP65 protection and a gasket seals the joint between the instrument enclosure and the panel The instrument may be installed in any panel providing the environmental limits shown i...

Page 6: ...IP65 seal between the instrument enclosure and the panel c Connect the panel wiring to the rear terminal block s as shown in Fig 5 To simplify installation the terminals are removable so that panel w...

Page 7: ...isplay may be calibrated to show the flow rate in engineering units Both the zero display at 4mA and the span display at 20mA are adjustable although for flow application the display at 4mA is usually...

Page 8: ...econds while the new information is stored in permanent memory All new BA558C rate totalisers are supplied calibrated as requested at the time of ordering If calibration information is not supplied th...

Page 9: ...liamps or the input as a percentage when the P push button is operated in the display mode Select PC for of span and 4 20 to display current See section 5 12 Display Description of function SCALE t To...

Page 10: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 11: ...or and Similarly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display...

Page 12: ...s have been correctly positioned press E to return to the main menu If the application requires flow rate to be the primary display i e shown on the large display the d P function enables the rate and...

Page 13: ...ive access to the sub menu 5 9 1 AC rejection FrE WARNING If the mains filter frequency is changed the rate display and the internal references if used must be recalibrated To provide maximum low freq...

Page 14: ...ress E to return to the main menu 5 12 Function of the P push button C P This parameter defines the function of the P push button when the BA558C is in the display mode Either the input current in mil...

Page 15: ...lect CLIP OFF from the main menu and press P to reveal the current setting This clip off threshold is shown as a percentage of total flow and may be adjusted in one percent increments using the Up or...

Page 16: ...ection 7 1 describes the preferred method of calibration using an external traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the BA558C internal 4 and 20mA references wh...

Page 17: ...ress the Up or Down push button until the second least significant digit and following decimal point of the total display flash This gives the required total display resolution of 0 1 Press P to move...

Page 18: ...to the main menu by pressing E Step 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no...

Page 19: ...nd by displaying root which is the first function in the main menu Steps Perform as described in the 3 to 7 previous calibration example see section 6 1 Step 8 Calibrate the rate display Scroll throug...

Page 20: ...e display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Reduce resolution of the rate display to mask flow noise Incorrect calibration Digital filter FrE...

Page 21: ...ilable for a rate alarm and shows which are fail safe i e output is in the alarm condition open when the 4 20mA input current is zero Similarly when programmed as a total alarm the output should be op...

Page 22: ...es the alarm function without changing the alarm parameters See section 8 3 3 tYPE Type of alarm Defines whether the alarm operates on the rate or total display See section 8 3 4 SPr1 Alarm setpoint 1...

Page 23: ...YPE This function conditions the alarm to operate on the rate or total display Alarm 1 and Alarm 2 may both be conditioned as rate or total alarms or one may be conditioned for rate and the other for...

Page 24: ...ing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the required hysteresis has been entered press E to return to the alarm menu e...

Page 25: ...etpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to 0000 8 3 12 Adjusting alarm setpoints from th...

Page 26: ...current limiting resistor in series with the supply will reduce the display brilliance 8 5 Additional front panel protection Although the BA558C has an IP65 sealed front panel for installations in hos...

Page 27: ...otal 5 6 d P 5 3 5 6 EnbL 8 3 2 8 3 3 Fault finding during commissioning 7 1 after commissioning 7 2 Flow indicator 2 2 Flow transmitter loops 3 1 Grand total 2 1 clear 5 3 5 10 Guarantee 7 5 HI LO 8...

Reviews: