Display
Summary of function
FiLtEr
Display filter
Is an adjustable digital filter to
reduce the noise on the rate display.
The filter has two parameters each
represented by a digit adjustable
between 0 and 9. The first digit
defines the amount of filtering
applied to the display, the second
digit the deviation from the displayed
rate at which the filter will be
overridden and the rate display will
move rapidly to the new value.
See section 6.20
up or dn
Direction of count
Determines whether pulses at inputs
A and b increment or decrement the
total display.
See section 6.21
CLr VAL
Reset value
Defines a preset number to which
the total display will be set when the
BA364G
Counter
is
locally
or
remotely
reset.
Enables
the
instrument to count down from a
preset number.
See section 6.22
LoC CLr
Local clear
Contains
sub-menu
with
two
functions enabling the total and the
grand total to be reset via the front
panel
push
buttons
while
the
Counter is in the display mode.
See section 6.23
Clr tot
When
on
is selected total display is
reset when
&
and
*
buttons are
operated simultaneously for more
than 3 seconds in the display mode.
See section 6.24
Clr Gtot
When
on
is selected the grand total
may be reset when
)
and
*
buttons are operated simultaneously
for more than 10 seconds in the
display mode - see section 2.2 for
details.
Note:
Once reset, the grand total
can not be restored.
See section 6.25
Display
Summary of function
Clr Gtot
Resets grand total to zero from
within configuration menu.
This function resets the grand total
to zero from within the configuration
menu when
CLr YE5
is selected.
Note
: Once reset, the grand total
can not be recovered.
See section 6.26
CodE
Access code
Defines a four digit alphanumeric
code that must be entered to gain
access to the configuration menu.
Default code 0000 disables the
security
function
and
allows
unrestricted
access
to
all
configuration functions.
See section 6.27
r5Et dEF
Reset to factory defaults
Returns the BA364G Counter to the
factory defaults shown in section 6.0
To
prevent accidental use the
request must be confirmed by
entering
5urE
before the reset will be
executed.
See section 6.28
19
Summary of Contents for BA364E
Page 1: ...Issue 5 9th July 2019 BA364G and BA364E Two Input Intrinsically safe Counter Issue 5 ...
Page 20: ...20 ...
Page 21: ...21 ...
Page 47: ...47 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 54: ...54 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...