background image

25

Display

Description of function

'Add'

Add a break-point

Adds a new break-point before the
displayed break-point.  The calibration
of existing break-points is not
changed, but the identification number
of subsequent break-points is
increased by one

'dEL'

Remove a break-point

Removes the displayed break-point
and joins the preceding break-point to
the following break-point with a
straight line.   The identification of
subsequent break-points is decreased
by one.

'InPut'

Defines the current at which break-
point occurs

Enables the required current at each
break-point to be defined without
having to input an accurate input
current to the indicator.

'diSP'

Defines display at break-point

Enables the indicator display at each
break-point to be defined.

Select 'SEt' from the main menu and press 

P

 once

to enter the 'Add' function, and again  to reveal the
current and total number of break-points.   Each
subsequent operation of the 

P

  push-button will

introduce an additional break-point.  When adding
a break-point to a calibrated indicator, the insertion
position can be selected using the 

Up

 and 

Down

push-buttons.

The delete break-point function 'dEL' operates in a
similar manner to the 'Add' function described
above.

When the required number of break-points has
been entered, return to the sub-menu by pressing

E

.  The indicator will display 'Add' or 'dEL'

depending upon the last function used.  The
required indicator display at each break-point can
now be entered, followed by the input current at
which each break-point occurs.

To enter the required display at any break-point
select 'diSP' from the sub-menu and press 

P

 which

will select the first break-point '0  n', where 'n' is the
total number of break-points selected.  The
selected break-point can be changed using the 

Up

and 

Down

 buttons.  When the required break-point

has been selected  press 

P

  to reveal the existing

display.  Using the 

Up

 and 

Down

 buttons and 

P

 to

move between digits set the revised display.
Press 

E

 to return to the sub-menu from which

another break-point  can be selected.   Repeat this
procedure for all the break-point displays to be
changed, and then return to the 'diSP' prompt in
the sub-menu by pressing E.

To enter the input current at which each break-
point occurs select 'InPut' from the sub-menu  and
press 

P

  which will select the first break-point '0  n'.

The selected break-point can be changed using
the 

Up

 and 

Down

 buttons.  When the required

break-point has been selected, press 

P

    to  reveal

the input current at which the break-point occurs.
Using the 

Up

 and 

Down

 buttons and 

P

    to  move

between digits, set the revised input current in mA.
Press 

E

 to return to the sub-menu from which

another break-point  can be selected.

Repeat this procedure for all the break-point input
currents to be changed, and then return to the
'InPut' prompt in the sub-menu by pressing 

E

.

9.4  Tare function

The tare function is a factory fitted software
accessory, primarily intended for use with weighing
systems.

When the tare software is installed, pushing and
holding the 

P

  button for more than 3 seconds sets

the indicator display to zero irrespective of the
input current, and activates the tare annunciator,
an arrow on the top left hand corner of the display.
Subsequent operation of the 

P

 push-button for less

than 3 seconds will toggle the indicator between
the normal gross display and the net display with
the tare annunciator activated.

The tare function allows an operator to quickly zero
the indicator display at any input current so that
subsequent  readings only show the change in
input since the 

P

  push-button was operated.  For

example when used with a weighing system, it
allows the weight of a container to be automatically
subtracted from the total gross weight so that only
the net  weight of  the contents is displayed.

Summary of Contents for BA324ND

Page 1: ...Issue 7 4th March 2014 BA324ND Type nL certified loop powered 4 digit field mounting indicator Issue 7 Only for replacement use after May 2013 Use BA324NE for new applications...

Page 2: ...eferences 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Units o...

Page 3: ...forward biased diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which...

Page 4: ...60079 Part 14 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted 3 3 4 20mA input terminals Input terminal...

Page 5: ...Fig 2 BA324ND in a transmitter loop In practice it is only necessary to ensure that in normal operation the maximum current flowing in the loop is less than 30mA In the example shown in Fig 2 this cu...

Page 6: ...ted to the internal EMC filters For maximum radio frequency interference rejection this terminal should be connected to a local earth or to a cable screen which is earthed in the safe area To prevent...

Page 7: ...and may be operated when a flammable atmosphere is likely to be present All the programming functions are contained in an easy to use menu which is shown diagramatically in Fig 6 Each function is sum...

Page 8: ...s the resolution of the least significant display digit May be set to 1 2 5 or 10 digits See section 6 3 d P Decimal point Positions the dummy decimal point between any of the digits or turns it off S...

Page 9: ...ial flowmeter Below 5 of flow the BA324ND display is forced to zero of full flow Current output mA 5 0 4 04 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This function defin...

Page 10: ...10...

Page 11: ...least significant digit has been adjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning sub menu Cond This sub menu allows the mains line frequency at whic...

Page 12: ...ith the default security code 0000 which allows unrestricted access to all programming functions To enter a new security code select COdE from the menu and press P which will cause the indicator to di...

Page 13: ...and press E to return to the main menu Step 4 Select frequency of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the...

Page 14: ...y of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the FrE function Using the Up or Down buttons select 50 and then...

Page 15: ...ay has a large voltage ripple content Unable to Incorrect Enter correct security enter the security code or fit security programme code link in override position Mode entered See Fig 7 8 2 Fault findi...

Page 16: ...intenance The mechanical condition of the instrument and electrical calibration should be regularly checked The interval between inspections depends upon environmental conditions We recommend that ini...

Page 17: ...A324ND can also be supplied with a blank or custom engraved stainless steel plate secured to the instrument terminal cover by two screws 9 2 Alarms The BA324ND can be supplied with two solid state sin...

Page 18: ...owing table summarises each of the alarm programme functions and includes a cross reference to more detailed information Again only the functions on alarm 1 are listed but alarm 2 has identical facili...

Page 19: ...een calibrated to display 0 with 4mA input and 10000 with 20mA input the two alarm setpoints may be positioned anywhere between 125 and 10125 To adjust the setpoint select SP1 or SP2 from the alarm me...

Page 20: ...can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 2 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been c...

Page 21: ...nt AcSP This function controls a separate menu which provides direct access to the alarm setpoints when the indicator is in the display mode See section 9 2 12 for a full description An operator may t...

Page 22: ...ressing E will return the display to the SP1 or SP2 prompt from which the other setpoint may be selected or the indicator may be returned to the display mode by pressing E again Direct access to the a...

Page 23: ...n can be selected using the Up and Down push buttons The delete break point function dEL operates in a similar manner to the Add function described above When the required number of break points has b...

Page 24: ...24...

Page 25: ...equired break point has been selected press P to reveal the existing display Using the Up and Down buttons and P to move between digits set the revised display Press E to return to the sub menu from w...

Page 26: ...i 30V dc Ii 100mA dc Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 15 Providing the supply voltage is less than 30V the backlight safety componen...

Page 27: ...re available for securing the BA324ND to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any pipe with outside diameter between 60 and 8...

Reviews: