background image

13

7.  CALIBRATION EXAMPLES

The following examples illustrate the two ways in
which a BA324ND indicator may be calibrated.

7.1  Using an external current source

The BA324ND indicator is required to display:

-50.0

with a 4mA input

1050.0

with a 20mA input

from a linear transducer.  Maximum display
resolution is required, the frequency of the mains
supply is 50Hz and the existing security code is
1209.  In the operating mode the indicator is
required to display the input current as a
percentage of span when the 

P

 push-button is

operated.

Step 1

Connect indicator to calibrator

Connect the indicator to an accurate
external current source.  Terminal 1
positive.  The indicator will
automatically perform the initialisation
routine described in section 2, and
then display the input current using
the existing calibration information.

Step 2

Enter programming mode

With an input current between 4 and
20mA put the indicator in the
programming mode by simultaneously
pressing 

P

 and 

E

.  The indicator will

respond by displaying 'COdE'.  Press

P

  to clear this prompt and set the

display to the security code 1209
using the 

Up

Down

 and 

P

 push-

buttons. Pressing 

E

 will enter the

code, and after a few seconds during
which the decimal points will be
scrolled, the first parameter 'root' in
the main menu will be displayed.

Step 3

Square root extraction

With 'root' displayed, press 

P

    which

will reveal the root extractor status.
The root extractor can be turned on or
off by the 

Up

 or 

Down

 buttons.  Select

'OFF', and press 

E

 to return to the

main menu.

Step 4

Select frequency of maximum
mains (line) rejection

Scroll though the main menu until
'Cond' is displayed.  Enter the sub-
menu by pressing 

P

 twice and select

the 'FrE' function.  Using the 

Up

 or

Down

 buttons select '50',  and then

press 

E

  twice to return to the main

menu.

Step 5

Define function of P push-button

Select 'C--P' from the main menu and
press 

P

 to reveal the function of the 

P

button in the display mode.  Select
percentage 'PC' and return to the
main menu by pressing  

E

Note:

  Because an input current

display in milliamps is not required, it
is not necessary to calibrate the two
internal references.

Step 6

Position dummy decimal point

Scroll though the main menu until
'd.P.' is displayed and then press 

P

.

Using the 

Up

 and 

Down

 push-buttons

position the dummy decimal point in
front of the least significant digit.
Press 

E

 to return to the main menu.

Step 7

Calibrate the display

Scroll through the main menu until
'CAL' is displayed.  Press 

P

 and the

indicator will request a 4mA input by
displaying  'ZErO'.  Set the input
current to 4.0000 ± 0.0004mA and
press 

P

 again which will reveal the

existing zero display.  Using the 

Up

,

Down

 and 

P

 push-buttons enter the

required zero display of  -50.0  Press

E

 to return to the 'ZErO' prompt.

Press the 

Up

 push-button and the

indicator will request a 20mA input by
displaying  'SPAn'.  Set the input
current to 20.0000 ± 0.0004mA and
again press 

P

  which will reveal the

existing display at 20mA.  Using the

Up

Down

 and 

P

 push-buttons enter

the required display of  1050.0
Press 

E

 twice to return to the main

menu.

Step 8

Return to the display mode

Following completion of calibration
return to the display mode by pressing

E.

Summary of Contents for BA324ND

Page 1: ...Issue 7 4th March 2014 BA324ND Type nL certified loop powered 4 digit field mounting indicator Issue 7 Only for replacement use after May 2013 Use BA324NE for new applications...

Page 2: ...eferences 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Units o...

Page 3: ...forward biased diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which...

Page 4: ...60079 Part 14 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted 3 3 4 20mA input terminals Input terminal...

Page 5: ...Fig 2 BA324ND in a transmitter loop In practice it is only necessary to ensure that in normal operation the maximum current flowing in the loop is less than 30mA In the example shown in Fig 2 this cu...

Page 6: ...ted to the internal EMC filters For maximum radio frequency interference rejection this terminal should be connected to a local earth or to a cable screen which is earthed in the safe area To prevent...

Page 7: ...and may be operated when a flammable atmosphere is likely to be present All the programming functions are contained in an easy to use menu which is shown diagramatically in Fig 6 Each function is sum...

Page 8: ...s the resolution of the least significant display digit May be set to 1 2 5 or 10 digits See section 6 3 d P Decimal point Positions the dummy decimal point between any of the digits or turns it off S...

Page 9: ...ial flowmeter Below 5 of flow the BA324ND display is forced to zero of full flow Current output mA 5 0 4 04 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This function defin...

Page 10: ...10...

Page 11: ...least significant digit has been adjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning sub menu Cond This sub menu allows the mains line frequency at whic...

Page 12: ...ith the default security code 0000 which allows unrestricted access to all programming functions To enter a new security code select COdE from the menu and press P which will cause the indicator to di...

Page 13: ...and press E to return to the main menu Step 4 Select frequency of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the...

Page 14: ...y of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the FrE function Using the Up or Down buttons select 50 and then...

Page 15: ...ay has a large voltage ripple content Unable to Incorrect Enter correct security enter the security code or fit security programme code link in override position Mode entered See Fig 7 8 2 Fault findi...

Page 16: ...intenance The mechanical condition of the instrument and electrical calibration should be regularly checked The interval between inspections depends upon environmental conditions We recommend that ini...

Page 17: ...A324ND can also be supplied with a blank or custom engraved stainless steel plate secured to the instrument terminal cover by two screws 9 2 Alarms The BA324ND can be supplied with two solid state sin...

Page 18: ...owing table summarises each of the alarm programme functions and includes a cross reference to more detailed information Again only the functions on alarm 1 are listed but alarm 2 has identical facili...

Page 19: ...een calibrated to display 0 with 4mA input and 10000 with 20mA input the two alarm setpoints may be positioned anywhere between 125 and 10125 To adjust the setpoint select SP1 or SP2 from the alarm me...

Page 20: ...can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 2 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been c...

Page 21: ...nt AcSP This function controls a separate menu which provides direct access to the alarm setpoints when the indicator is in the display mode See section 9 2 12 for a full description An operator may t...

Page 22: ...ressing E will return the display to the SP1 or SP2 prompt from which the other setpoint may be selected or the indicator may be returned to the display mode by pressing E again Direct access to the a...

Page 23: ...n can be selected using the Up and Down push buttons The delete break point function dEL operates in a similar manner to the Add function described above When the required number of break points has b...

Page 24: ...24...

Page 25: ...equired break point has been selected press P to reveal the existing display Using the Up and Down buttons and P to move between digits set the revised display Press E to return to the sub menu from w...

Page 26: ...i 30V dc Ii 100mA dc Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 15 Providing the supply voltage is less than 30V the backlight safety componen...

Page 27: ...re available for securing the BA324ND to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any pipe with outside diameter between 60 and 8...

Reviews: