background image

11

When using the internal calibrator, the following
procedure should be followed. The adjustments
may be performed with any input current between
4 and 20mA.

Step 1

Put the suppression / elevation, zero,
span and decimal point links in the
required position.  Put the root / linear
link in the root position.

Step 2

Put the calibrator link in the 4mA
position and adjust the indicator zero
potentiometer to give the required
display at 4mA.

Step 3

Put the calibrator link in the 20mA
position and adjust the indicator span
potentiometer to give the required
display at 20mA.

Step 4

Repeat steps 2 and 3 until  both
calibration points are correct.  The
span and zero controls are almost
independent so it should only be
necessary to repeat each adjustment
twice.

Step 5

Return  the  calibrator  link  to  the
'indicate' position. The indicator will
now respond to the 4/20mA input
current with the revised calibration.

8.3  Root extractor

The BA304ND can be supplied with a square root
extractor which enables the indicator to accurately
display the output from a differential flow meter in
linear engineering units between 10 and 100% of
full flow (4.16 to 20mA).  The lineariser continues
to operate with reduced accuracy down to 2.5% of
maximum flow, alternatively clip-off can be
selected which will force the display to zero at
flows below 5% (4.04mA). The location of the clip-
off link is shown in Fig 7. Access to the link is
gained by carefully removing the indicator
assembly from the enclosure as follows. Remove
the terminal cover by unscrewing the two ‘A’
screws which will reveal two concealed ‘D’ screws.
Unscrew the four ‘D’ screws and carefully lift off
the front of the instrument enclosure. Fig 4 shows
the location of these screws. Finally remove
screws securing the electronic assembly.

Fig 7 Location of root extractor clip-off link

When calibrating a BA304ND fitted with a root
extractor the indicator zero potentiometer should
be adjusted to give the required display at 10% of
flow (4.16mA). The indicator zero potentiometer
should not be used to set the display to zero with a
4mA input. Zero suppression or elevation may not
be used, i.e.  4mA must correspond to zero flow.

For reference, the following table shows the output
current from a non-linearised differential flowmeter.

% of full flow

   Current output mA

2.5

4.01

10.0

4.16

25.0

5.00

50.0

8.00

75.0

13.00

100.0

20.00

A root extractor can not be fitted to an instrument
with an internal calibrator.

8.3.1  Calibration example with root extractor

The BA304ND is required to display rate of flow in
gallons per minute, with a resolution of 0.1 gallons.
The differential flowmeter has an output of 20mA
at a flow rate of 140.0 gallons per minute

Summary of Contents for BA304ND

Page 1: ...issue 8 4th March 2014 BA304ND Type nL certified loop powered 3 digit field mounting indicator issue 8 Only for replacement use after May 2013 Use BA304NE for new applications...

Page 2: ...on example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments...

Page 3: ...wer the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital...

Page 4: ...mperatures between 20 and 60 C Used with gases in groups Group A propane Group B ethylene Group C hydrogen Used with gases having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C or...

Page 5: ...alyser drives a BA304ND Again it is necessary to ensure that the loop complies with the two design requirements listed in section 4 1 Fig 3 Remote indication 5 INSTALLATION 5 1 Location The BA304ND in...

Page 6: ...re 5 3 EMC The BA304ND complies with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs Fig 5 Dimensions and terminal conn...

Page 7: ...plug in link shown in Fig 6 When calculating the required span and zero settings the decimal point should be ignored 6 4 Reverse action Normally the BA304ND display increases as the input current inc...

Page 8: ...8 Fig 6 Position of plug in links and potentiometers shown with control cover removed...

Page 9: ...n not enter the enclosure Before replacing control terminal covers ensure that the sealing gaskets are undamaged and free from dirt and foreign bodies If a BA304ND fails after it has been functioning...

Page 10: ...dirt and foreign bodies To gain access to the display label remove the terminal cover by unscrewing the two A screws which will reveal two concealed D screws Unscrew the four D screws and carefully l...

Page 11: ...ely clip off can be selected which will force the display to zero at flows below 5 4 04mA The location of the clip off link is shown in Fig 7 Access to the link is gained by carefully removing the ind...

Page 12: ...d wiring are required but the indicator voltage drop is increased Alternatively the separatly powered backlight has a bright orange output which enhances daylight viewing but additional field wiring a...

Page 13: ...t secured by two worm drive hose clips Will clamp to any pipe with an outside diameter between 60 and 80mm BA393D Heavy duty stainless steel bracket secured by a V bolt Will clamp to any pipe with an...

Reviews: