background image

5

There are two basic design requirements:

1.  In normal operation the voltage and

current applied to terminals 1 and 3 of the
BA304ND must not exceed:

Ui

=

4V dc

Ii

=

30 mA dc

Providing the maximum input current in
normal operation is less than 30mA, the
maximum voltage between the indicator
terminals will automatically be limited by
the internal safety components.

2. 

The 4/20mA loop must be able to tolerate
the additional 1.1V required to operate the
indicator.

In practice it is only necessary to ensure that in
normal operation the maximum current flowing in
the loop is less than 30mA.  In the example shown
in Fig 2 this current is determined by the maximum
current from the transmitter.

The sum of the maximum voltage drops of all the
components in the loop must be less than the
minimum power supply voltage. Considering the
example shown in Fig 2:

Minimum operating voltage of 2-wire Tx 

10.0

Maximum voltage drop caused by controller

5.0

Maximum voltage drop caused by BA304ND

1.1

Maximum voltage drop caused by cables

0.4

                                                                        _____

16.5V

Therefore at 20mA the power supply in this
example must have an output greater than 16.5V

4.2  Remote indication

A BA304ND indicator may be driven from any
4/20mA signal to provide remote indication.  Fig 3
shows a typical application in which the output
from a gas analyser drives a BA304ND.  Again it is
necessary to ensure that the loop complies with
the two design requirements listed in section 4.1

Fig 3 Remote indication

5.  INSTALLATION

5.1  Location

The BA304ND indicator is housed in a robust IP66
glass reinforced polyester (GRP) enclosure
incorporating an armoured glass window and
stainless steel fittings.  This makes it suitable for
exterior mounting in most industrial applications,
including off-shore and waste water treatment.
Please contact BEKA associates if high vibration is
anticipated.

The BA304ND is surface mounting, but may be
pipe or stem mounted using the accessory kits
described in sections 8.5 and 8.6 of this manual.

The field terminals and the two enclosure mounting
holes are located in a separate compartment with
a sealed cover allowing the instrument to be
installed without exposing the display assembly or
controls. Terminals 2 and 4 are internally joined
and may be used for linking the return 4/20mA wire
- see Fig 2.  Similarly, terminals 5 and 6 are
internally joined and may be used for linking the
cable screens. The BA304ND earth terminal is
connected to the internal EMC filters. For
maximum radio frequency interference rejection
this terminal should be connected to a local earth,
or to an earthed cable screen. To prevent
circulating currents, cable screens should only be
earthed at one point in the safe area.

The BA304ND enclosure is supplied with a
bonding plate to ensure electrical continuity
between the three conduit / cable entries.

Summary of Contents for BA304ND

Page 1: ...issue 8 4th March 2014 BA304ND Type nL certified loop powered 3 digit field mounting indicator issue 8 Only for replacement use after May 2013 Use BA304NE for new applications...

Page 2: ...on example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments...

Page 3: ...wer the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital...

Page 4: ...mperatures between 20 and 60 C Used with gases in groups Group A propane Group B ethylene Group C hydrogen Used with gases having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C or...

Page 5: ...alyser drives a BA304ND Again it is necessary to ensure that the loop complies with the two design requirements listed in section 4 1 Fig 3 Remote indication 5 INSTALLATION 5 1 Location The BA304ND in...

Page 6: ...re 5 3 EMC The BA304ND complies with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs Fig 5 Dimensions and terminal conn...

Page 7: ...plug in link shown in Fig 6 When calculating the required span and zero settings the decimal point should be ignored 6 4 Reverse action Normally the BA304ND display increases as the input current inc...

Page 8: ...8 Fig 6 Position of plug in links and potentiometers shown with control cover removed...

Page 9: ...n not enter the enclosure Before replacing control terminal covers ensure that the sealing gaskets are undamaged and free from dirt and foreign bodies If a BA304ND fails after it has been functioning...

Page 10: ...dirt and foreign bodies To gain access to the display label remove the terminal cover by unscrewing the two A screws which will reveal two concealed D screws Unscrew the four D screws and carefully l...

Page 11: ...ely clip off can be selected which will force the display to zero at flows below 5 4 04mA The location of the clip off link is shown in Fig 7 Access to the link is gained by carefully removing the ind...

Page 12: ...d wiring are required but the indicator voltage drop is increased Alternatively the separatly powered backlight has a bright orange output which enhances daylight viewing but additional field wiring a...

Page 13: ...t secured by two worm drive hose clips Will clamp to any pipe with an outside diameter between 60 and 80mm BA393D Heavy duty stainless steel bracket secured by a V bolt Will clamp to any pipe with an...

Reviews: