Page  5

Selecting the type of gas monitored for each sensor

The switch number 3 is used to select  reading the type of gas that the probe is connected to detect.
The LEL reading is obtained by shifting the switch to ON.

Explosive gas.

The ppm reading is obtained by shifting the switch to OFF

.

Toxic gas.

Positive  Safety-  Working  mode  of  the  relay  and  the  main  alarm

Switch  1  –  Selection  of  the  positive  safety
In  the  ON  position,  the  positive  safety  function  is  enabled.
The  relay  is  energized  after  performing  the  step  of  waiting  and  switches  when  the  BX150  is  main  alarm
In  the  OFF

 

position,  the  positive  safety  function  is  disabled.

The  relay  is  energized  only  when  the  BX150  goes  into  the  mainl  alarm

Switch  2  -  Working  mode  of  the  main  alarm  relay.
In  the  ON

 

(continuous)  position,  the  relay  remains  closed  until  the  N  button  is  pressed.

In  the    OFF

 

  (impulse)  position,  the  relay  remains  closed  for  20  seconds,  and  then  disenergizes  afterwards.

Micro-switches  1  Positive  safety
Micro-switches 2 Working  mode  of  the  main  alarm
relay

Micro-switch  (3)  to  select  the  type  of  gas
monitored.
Positione  ON  reading  in  LEL  -  Explosive  gas
In  posizione  OFF  lettura  in  ppm  -  Toxic  gas

Description of Micro-switches

Summary of Contents for BX150

Page 1: ...he BX150 control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and or explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX150 is suitable for civil and industrial applications The BX150 control unit has two danger levels 1st LEVE...

Page 2: ...mage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the control unit could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Precautions 90 mm 102 mm 112 mm 10 mm 43 65 mm 90 30 mm Cuttingpanel size Mains Power 230VAC 50 60Hz 10 Secondary Power Through Batter...

Page 3: ...eon 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Electrochimical IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochimical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochimical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochimical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2...

Page 4: ...C GAS selection LED This LED lights up when the internal micro switch is switched to CO 7 EXPLOSIVE GAS selection LED This LED lights up when the internal micro switch is switched to GAS 8 FAULT LED This LED will light up when the connected probe is faulty if there is an interruption in the cable connection or if an error was made during wiring 9 OVER LOAD LED probe overload If this LED turns on i...

Page 5: ...r performing the step of waiting and switches when the BX150 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX150 goes into the mainl alarm Switch 2 Working mode of the main alarm relay In the ON continuous position the relay remains closed until the N button is pressed In the OFF impulse position the relay remains closed for 20 seco...

Page 6: ...Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that signal cables should be separated from power cables An automatic cut off switch appropriately identified as device sectioning of the detector should be incorporated in the electrical system adequately located and easily acce...

Page 7: ...hold Alarm Solenoid valves Ph N 230 VAC NC NA Solenoid valve GAS and Sirens 12 VDC Powersupply 230 12V Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA Control ...

Page 8: ...ld Alarm Solenoid valves Powersupply 230 12V Ph N 230 VAC 230 VAC Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 Electrical Connections If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA ...

Page 9: ...You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to d...

Page 10: ...ins power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX150 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short ci...

Page 11: ...Page 11 NOTES ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Reviews: