Battery
Battery run time
90 minutes minimum
Battery type
Sealed, Maintenance-Free, AGM, VRLA type
Unit Rating (KW)
6
8
10
15
17
Nominal dc voltage
144 VDC
192 VDC
192 VDC
240 VDC
240 VDC
Overcurrent protection
Circuit Breaker
Packaging
Batteries Housed in Same Enclosure and/or additional battery cabinet for other battery run time
Monitoring and communications
LCD Screen
Input Voltage; Battery Charger; UPS Output; On Battery; Low Battery; Summary Alarm
Indicators
LCD Display Panel (Back lit)
Relay interface
Dry Contacts for: Low Battery, On Bypass, Summary Alarm, Input Fail
Contact rating
125 Volts (AC or DC) Maximum; 1.25 Amperes Maximum; 30 Watts / 50 VA Maximum
Interface connection
Hard Wired (Terminal Block)
Environmental
Surge with standability
ANSI C62.41-1980 categories A & B
Operating temperature
Meets NEMA requirements
Operating relative humidity
0 to 95% non-condensing
Altitude
Up to 6,000 feet (1,829 meters) with no de-rating
Cooling
Air cooled-forced air (fan)
Physical
Unit Rating
6KW
8KW
10KW
15KW
17KW
Dimensions (inches) W x H x D
39 x 68 x 18
51 x 70 x 30.5
Construction
Painted Steel Enclosure, Lockable Double front door, Full length hinged, for indoor installation,
Color
Black
Accessibility
Front all Servicing is through the front no side or rear access required
Beghelli U
.S.A., 3250 Corporate Way, Miramar, Florida, Tel: (800) 726-4316 Tel: (954) 442-6600 Fax: (954) 442-6677
NOVA
6, 8, 10, 15 & 17KW