• F-07 Rapid linear decelerate time when power cut off.(Fast stop)
Deceleration ramp time after mains loss (F-05 =0 or 2) or when fast stop
activated (see F-19).
When F-05 =2 and F-07 =0, activation the fast stop disables the drive
without braking (effectively coasting to stop)
• F-08 motor rated current
Rated (nameplate) current of the motor (Amps). In HVAC (F-06=1)
mode, the rated motor current limit is increased, allowing F-08 to be set
to a higher level.
• F-09 motor rated rotate speed.
Rated (nameplate) frequency of the motor.
Changing F-09, resets F-02, F-10, F-26 & F-28 to 0, & F-01= F-09
• F-10 motor output rated voltage
When non-zero, Speed is displayed in RPM in parameters F-01, F-02,
F-20 ….F-23, F-27 and F-28
Example, Motor rated frequency is 50Hz, Speed can be set from
600-3000RPM/min; when motor speed is non-zero, rotary speed should
be shown on the unit of RPM
• F-11 Low speed voltage compensation (Voltage boost).
Applies an adjustable boost to the drive voltage output at low speed to
assist with starting ‘sticky’ loads, for continuous applications at low
speed use a forced ventilated motor
• F-12 Terminal or keyboard control select (controlling mode)
Select “Start/Stop” through terminal controlling or keyboard controlling