If user want the motor stops work automatically (inertia stopping),
please sets F-05 to 1.
•V/F curve select F-06.
General loading F-06=0.
Such as fan, water pump etc. which are belonging to variable torque
loading, Pls set F-06=1, which will reduce the energy wastage when
motor run at low speed.
• Motor rated current, rated frequency and rated RPM(F-08, F-09, F-10).
Parameters should be set according to the nameplate on the motor.
When F-10 = 0, The Speed value appears with HZ.
If we set F-10 as motor rated RPM, which will help to improve slip
compensation function under different loading conditions
• Low speed voltage compensation (F-11).
Favorable to start motor smoothly, Maximum value of voltage
compensation up to 25%.
• Controlling methods select (F-12).
Terminal controlling method is for long distance control use.
Keyboard controlling method is for trial operation or handle manually.
• “Extended menu access” select(F-15~F-40)
“Extended menu access” is designed for inverter application experts,
engineers or technicians. General users don’t need to use it.