Technical data, mounting, wiring
PS3011-2440-0000
15
Version: 1.0
Fig. 7: Extra power after switching on; extra power after short circuit or overload
3.5
Hold-up time
The hold-up time is the time during which the output voltage of a power supply unit remains within the
specification after a loss of input power. The hold-up time depends on the output load. Without load the hold-
up time can be several seconds. The green DC-OK LED also lights up during this time.
AC 100 V
AC 120 V
AC 230 V
Hold-up
time
Typ.
54 ms
54 ms
54 ms
At 24 V, 20 A, see Fig.
Hold-up time over input
voltage
min.
45 ms
45 ms
45 ms
At 24 V, 20 A, see Fig.
Hold-up time over input
voltage
Typ.
27 ms
27 ms
27 ms
At 24 V, 40 A, see Fig.
Hold-up time over input
voltage
min.
23 ms
23 ms
23 ms
At 24 V, 40 A, see Fig.
Hold-up time over input
voltage
Fig. 8: Hold-up time over input voltage; switch-off behavior, definitions