Technical data, mounting, wiring
PS3011-2440-0000
12
Version: 1.0
3.2
DC input
Do not use the power supply unit with DC input voltages!
3.3
Input inrush current
Active inrush current limitation limits the inrush current surge to a negligible value after the input voltage is
switched on. The input inrush current is usually lower than the continuous input current.
AC 100 V
AC 120 V
AC 230 V
Input inrush
current
*)
Max. 25 A
peak
22 A
peak
16 A
peak
over the entire temperature range;
Mains interruptions > 1 s
Typ. 20 A
peak
17 A
peak
11 A
peak
over the entire temperature range;
Mains interruptions > 1 s
Inrush energy
Max. 5 A²s
5 A²s
5 A²s
over the entire temperature range;
Mains interruptions > 1 s
*)
The charge current of the interference suppression capacitors during the first few microseconds after
switching on is not taken into account.
Fig. 3: Typical switch-on behavior at nominal load, 230 Vac input voltage and 25°C ambient temperature