Technical data, mounting, wiring
PS2031-2410-0000
22
Version: 1.0
3.11
Front side and operating elements
Fig. 10: Front PS2031-2410-0000
Input terminals (screw terminals)
Designation (A)
Description
L1, L2, L3
Mains input L1, L2, L3
PE input (protective conductor)
Output terminals (screw terminals)
Designation (B)
Description
+
two identical positive poles, positive output
-
two identical negative poles, negative output
Potentiometer for the output voltage
Designation (C)
Description
Potentiometer cover
Open the flap to adjust the output voltage. Factory setting: 24.1 V
"Parallel Use" or "Single Use" mode
Designation (D)
Description
Jumper for "Single Use"
or "Parallel Use"
Set the jumper to "Parallel Use" if devices are connected in parallel to increase the output power.
In order to distribute the load current among the individual power supply units, the "Parallel Use" mode
regulates the output voltage so that the voltage at zero load is approx. 4% higher than at nominal load.
A missing jumper corresponds to "Single Use" mode, which is the factory setting.
DC OK LED
Designation (E)
Description
Push-in terminals
13 / 14
Monitors the output voltage of the active power supply.
See chapter on DC OK relay contact for more information.