Technical data, mounting, wiring
PS2031-2410-0000
24
Version: 1.0
3.13
Environment
Environment
Operating temperature
1)
-25°C to +70°C
Reduction of the output power according to Fig.
Output
current over ambient temperature
Storage temperature
-40°C to +85°C
For storage and transport
Output load reduction
(derating)
3.2W/°C / 6W/°C
+45°C to +60°C / +60°C to +70°C
15W/1000m or 5°C/1000m
For altitudes >2000m, see Fig.
Output current over in-
stallation altitude
9W/-5kPa or 3°C/-5kPa
For atmospheric pressures <80kPa, see Fig.
Output cur-
rent over installation altitude
The derating is not hardware-controlled. The user must take this into account in order to stay be-
low the reduced current limits, so that device overload is avoided.
Moisture
5 to 95% r.h.
According to IEC 60068-2-30
Do not energize if there is condensation.
Atmospheric pressure
110-47kPa
see Fig.
Output current over installation altitude
Installation altitude
up to 6000m
see Fig.
Output current over installation altitude
Overvoltage category
III
According to IEC 60664 -1, installation altitudes up to
2000m
II
According to IEC 60664 -1, installation altitudes above
2000m and atmospheric pressures between 80 and
47kPa
Degree of pollution
2
According to IEC 62477-1, non-conductive
Oscillation, sinusoidal
2)
2–17.8Hz: ±1.6mm;
17.8–500Hz: 2 g
2 hours/axis
According to IEC 60068-2-6
Impacts
2)
30g 6ms, 20g 11ms
3 impacts/direction, 18 impacts in total
According to IEC 60068-2-27
LABS-free
The device does not release any silicones or other paint-wetting impairment substances and is
suitable for use in paint shops.
Corrosive gas
Tested according to ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4 for a
service life of at least 10 years in these environments.
Audible noises
In the event of no-load, overload or short circuit, the power supply unit emits audible noises.
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2cm below the device.
2)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of
1.3mm and standard mounting position.
Fig. 11: Output current over ambient temperature; output current over installation altitude