Data structures of the modules
KL85xx und KL9309
77
Version: 2.1.0
Process data
Input data
Data byte 1
Data byte 1 indicates the positions of the switches (auto/man).
Bit
Name
Description
0
enAutoCh1
1
bin
Switch of channel 1 is set to auto: the PLC controls this channel.
1
enAutoCh2
1
bin
Switch of channel 2 is set to auto: the PLC controls this channel.
...
...
...
7
enAutoCh8
1
bin
Switch of channel 8 is set to auto: the PLC controls this channel.
Data byte 2
Data byte 2 indicates the positions of the switches (off/on).
Bit
Name
Description
0
Switch1
0
bin
Switch of channel 1 is set to off
1
bin
Switch of channel 1 is set to on
1
Switch1
0
bin
Switch of channel 2 is set to off
1
bin
Switch of channel 2 is set to on
...
...
...
7
Switch1
0
bin
Switch of channel 8 is set to off
1
bin
Switch of channel 8 is set to on
Output data
Data byte 1
Data byte 1 sets the outputs in automatic mode.
Bit
Name
Description
0
setCh1
1
bin
Output 1 is set.
1
setCh2
1
bin
Output 2 is set.
...
...
...
7
setCh8
1
bin
Output 8 is set.
Data byte 2
Has no function (reserved) in process data mode, but is used for register communication.
Data byte 3
Data byte 3 sets the LEDs of the channels to green.
Bit
Name
Description
0
LED 1 green
1
bin
LED 1 lights up green
1
LED 2 green
1
bin
LED 2 lights up green
...
...
...
7
LED 8 green
1
bin
LED 8 lights up green
Data byte 4
Data byte 4 sets the LEDs of the channels to yellow.
Summary of Contents for KL85 Series