![Beckhoff KL85 Series Documentation Download Page 65](http://html1.mh-extra.com/html/beckhoff/kl85-series/kl85-series_documentation_2719270065.webp)
Data structures of the modules
KL85xx und KL9309
65
Version: 2.1.0
• Register R63: 0x0000
R8: Terminal description
The name of the terminal is contained in register R8.
KL8519: 0 x 2147 (8519
dec
)
R9: Firmware version
Register R9 contains the ASCII coding of the terminal's firmware version, e.g.
0x3141 = '1A'
. The
'0x31'
corresponds here to the ASCII character
'1'
, while the
'0x41'
represents the ASCII character
'A'
.
This value cannot be changed.
R12: Minimum data length of a channel
R16: Hardware version number
Register R16 contains the hardware version of the terminal.
R31: Code word register
• If you write values into the user registers without first entering the user code word (0x1235) into the
code word register, the terminal will not accept the supplied data.
• If you write values into the user registers and have previously entered the user code word (0x1235) in
the code word register, these values are stored in the RAM registers and in the SEEPROM registers
and are therefore retained when the terminal is restarted.
The code word is reset when the terminal is restarted.
R32: Disable Channel LED
Using this register you can deactivate the status LEDs of the individual channels.
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
disLED_Ch16
disLED_Ch1
5
disLED_Ch1
4
disLED_Ch13
disLED_Ch12
disLED_Ch11 disLED_Ch10 disLED_Ch9
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
disLED_Ch8
disLED_Ch7 disLED_Ch6 disLED_Ch5
disLED_Ch4
disLED_Ch3
disLED_Ch2
disLED_Ch1
Key
Bit
Name
Description
default
R32.15
disLED_Ch16
0
bin
The LED indicates the state of input 16. Further properties can be set with R33,
R34 and R35.
0
bin
1
bin
The LED does not indicate the state of input 16. However, the state of input 16
continues to be transmitted to the PLC. In addition the PLC can now switch the
LED selectively to green or red.
R32.14
disLED_Ch15
0
bin
The LED indicates the state of input 15. Further properties can be set with R33,
R34 and R35.
0
bin
1
bin
The LED does not indicate the state of input 15. However, the state of input 15
continues to be transmitted to the PLC. In addition the PLC can now switch the
LED selectively to green or red.
...
...
...
...
R32.0
disLED_Ch1
0
bin
The LED indicates the state of input 1. Further properties can be set with R33,
R34 and R35.
0
bin
1
bin
The LED does not indicate the state of input 1. However, the state of input 1
continues to be transmitted to the PLC. In addition the PLC can now switch the
LED selectively to green or red.
R33: LED Set Color
Using this register you can define the color for the status LEDs of the individual channels (green or red).
Summary of Contents for KL85 Series