Comissioning and Configuration
EP9214-0023 and EP9224-0023
84
Version: 2.3.1
4.6.2.1.8
Index F707 DPO Outputs Device
Index
Name
Meaning
Data type
Flags
Default
F707:0
DPO Out-
puts Device
UINT8
RO
0x11 (17
dec
)
F707:01
Enable Con-
trol Via
Fieldbus
0
bin
: All outputs are set to their default values
(80X0:02, 80X0:03)
1
bin
: All outputs are set according to their PDOs
(70X0:01, 70X0:02)
boolean
RO
0x00 (0
dec
)
F707:04
Global Re-
set
All error bits are reset
boolean
RO
0x00 (0
dec
)
F707:11
Reset Ex-
tended Diag
Data
Peak Values and time stamps from F607 are reset
boolean
RO
0x00 (0
dec
)