![Beckhoff ELX3312 Operating Manual Download Page 29](http://html1.mh-extra.com/html/beckhoff/elx3312/elx3312_operating-manual_2719618029.webp)
Mounting and wiring
ELX3312 and ELX3314
29
Version: 1.3.0
LED displays
LED
Color
Meaning
Run
green
This LED indicates the terminal's operating state:
off
State of the EtherCAT State Machine:
INIT
= initialization of the terminal or
BOOTSTRAP
= function for firmware updates of the terminal
flashing State of the EtherCAT State Machine:
PREOP
= function for mailbox
communication and different standard-settings set
single
flash
State of the EtherCAT State Machine:
SAFEOP
= verification of the Sync
Manager channels and the distributed clocks.
Outputs remain in safe state
on
State of the EtherCAT State Machine:
OP
= normal operating state; mailbox
and process data communication is possible
Error Ch 1 red
The measurement value of channel 1 is in an invalid range of the characteristic curve.
Possible short circuit or wire breakage at channel 1.
Error Ch 2 red
The measurement value of channel 2 is in an invalid range of the characteristic curve.
Possible short circuit or wire breakage at channel 2.