![Beckhoff ELX3312 Operating Manual Download Page 13](http://html1.mh-extra.com/html/beckhoff/elx3312/elx3312_operating-manual_2719618013.webp)
Product overview
ELX3312 and ELX3314
13
Version: 1.3.0
2.2
ELX3314 - Introduction
Fig. 5: ELX3314 - 4-channel analog input terminal for thermocouples, 16 bit, Ex i
The ELX3314 analog input terminal allows the direct connection of thermocouples located in hazardous
areas classified Zone 0/20 or 1/21. The circuitry of the ELX3314 can operate sensors with 2-wire technology.
Linearization is possible over the entire freely selectable temperature range. The error LEDs indicate a
broken wire. Compensation for the cold junction is achieved through internal temperature measurement.
Millivolt measurement is also possible with ELX3314.