![Beckhoff EL1052 Documentation Download Page 12](http://html.mh-extra.com/html/beckhoff/el1052/el1052_documentation_2719587012.webp)
Product overview
EL1052, EL1054
12
Version: 1.1
2.2
Technical data
Technical data
EL1052
EL1054
Number of inputs
2
4
Technology
NAMUR
Signal type
binary, current input for NAMUR sensors
Specification
NAMUR DC current switching amplifier (IEC 60947‑5‑6)
Connection technology
2-wire
“0“ signal current
≤ 1.2 mA
“1“ signal current
≥ 2.1 mA
Switching hysteresis
350 µA typ.
Shortcut current
7.8 mA typ.
Error detection
I ≤ 200 µA (wire break), I ≥ 7.0 mA (shortcut)
Switching frequency max.
5 kHz (duty cycle 50 %)
Open circuit voltage
8.2 V
DC
typ.
Reverse voltage protection
35 V
DC
max. (I1 or I2 in “no current state” against 0 V)
Internal resistance
according I/U‑diagram in IEC 60947‑5‑6, par. 9‑1
Distributed Clocks
-
Voltage power supply for electronics
24 V
DC
via power contacts
Current consumption E-bus
40 mA typ.
50 mA typ.
Current consumption power contacts 20 mA typ. + load
40 mA typ. + load
Electrical isolation
500 V (E-bus/field potential)
Bit width in the process image
4 state bits
8 state bits
Configuration
no address or configuration setting
Special features
integrated reverse voltage protection
Max. sensor wire length
The wire length from the EtherCAT terminal to the sensor/encoder
must have max. 30 m without any action of protection. For larger wire
lengths a proper over voltage protection (surge protection) is
required.
Weight
approx. 60 g
Permissible ambient temperature
range during operation
-25°C ... + 60°C
0°C ... + 55°C
Permissible ambient temperature
range during storage
-40°C ... + 85°C
-25°C ... + 85°C
Relative humidity
95 %, no condensation
Dimensions (W x H x D)
ca. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 /
EN 60068-2-27,
increased mechanical load
capacity
according to EN 60068-2-6/EN
60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class
IP20
Installation pos.
variable
Pluggable wiring
for all ESxxxx terminals
Approvals
CE
IECEx
Summary of Contents for EL1052