Operation

During operation, frequency converters can have – depending on their type of protection – 
electrically charged, uncovered, and possibly even moving or rotating parts, as well as hot 
surfaces. 

The device is charged with dangerous voltage for up to 5 minutes after being switched off. 
Opening the device or removing the covers or the operating unit is not permitted until 5 mi-
nutes after the voltage to the device has been switched off. Before switching on the power 
supply voltage all covers need to be reattached.

Even if the motor is at a standstill (for instance because of electronic blockage, blocked drive 
or output terminal short circuit) the power cable terminals, motor terminals and terminals for 
the brake resistor may still carry dangerous voltages. A motor standstill does not mean that 
there is a galvanic separation from the mains.

Notice

, under certain settings, the converter can start up automatically when switched on 

from the mains side. 

Systems into which the frequency converters are installed must, if necessary, be equipped 
with additional monitoring and protective devices according to the relevant safety regulations, 
i.e. laws for technical tools and appliances, accident preventions regulations, and so forth. 

There is a risk of serious injury for persons or material damage if required covers are removed 
without authorisation, if the device or its components are used improperly, or if installed or 
operated incorrectly. 

Electrically charged parts and line connections must not be touched directly after frequency 
converters are disconnected from the supply voltage, as the capacitors may be charged. 
Observe the corresponding signs about this on the frequency converters.

During operation all covers must be kept closed.

The frequency converter is maintenance-free under normal operating conditions. If the air is 
dusty, the cooling surfaces should be cleaned regularly with compressed air.

WARNING! DANGER TO LIFE!

The power pack may still be charged with voltage for up to 5 minutes after being switched 
off from the mains. Converter terminals, motor feeder lines and motor terminals may carry 
voltage.

Touching open or exposed terminals, lines and device parts can cause serious injuries 
and even death!

CAUTION

Children and the general public are prohibited from accessing the device.

The device may be used only as intended by the manufacturer. Unauthorised modifications 

and use of spare parts and auxiliaries that are not sold or recommended by the manufac-

turer of the device can cause fires, electrical shocks and injuries.

Store these operating instructions where they are easily accessible and place them in 
every user's hands.

The heat sink and other metallic parts can reach temperatures of more than 70 °C. 

Keep sufficient space to neighbouring components.
When working on the components allow for sufficient cooling time.

Warning: 

This is a product of the limited sales class acc. to IEC 61800-3. In a residential environ-
ment this product can cause high-frequency interferences, in which case the user can be 
required to take suitable measures. 

A suitable measure would be the employment of a recommended line filter.

Summary of Contents for VariAir VAU4/3

Page 1: ...www becker international com 1 28100241101 11 12 operating instructions Frequency converter vAU4 3 QUICK START GUIDE ...

Page 2: ...ns The latter should be read thoroughly before initial start up The quick start guide contains safety instructions and helps the user to put the basic model of the VAU 4 3 into operation and to operate it with the default settings Intended use i Frequency converters are components that are intended for installation into electrical systems or machines When being installed into machines the commissi...

Page 3: ...r devices that are es pecially sensitive to static electricity Therefore please avoid touching the circuit boards or components with your hands or with metallic objects Only the screws of the terminal strips may be touched by insulated screwdrivers when wires are connected The frequency converter is intended for permanent connection only and may not be operated without an effective earth connectio...

Page 4: ...y charged parts and line connections must not be touched directly after frequency converters are disconnected from the supply voltage as the capacitors may be charged Observe the corresponding signs about this on the frequency converters During operation all covers must be kept closed The frequency converter is maintenance free under normal operating conditions If the air is dusty the cooling surf...

Page 5: ...Rel 2 Terminal Connection L1 L2 L3 Mains feeder phase L1 L2 L3 PE Mains feeder earth line PE U V W Connection strands motor winding U V W X Y Z Feeder phase external ventilator phase L1 L2 L3 optional Connection terminals of the bottom row of the double decker terminal block Terminal Connection 1 24 V SELV 1 24 V DC fixed voltage output 2 Digital 1 Digital input 1 Digital 2 Digital input 2 Digital...

Page 6: ... switch block 1 with 4 switches Setting Function DIP switch 1 OFF Speed set operation ON Controlled operation DIP switch 2 OFF No control via RS485 field bus interface ON Control via RS485 field bus interface DIP switch 3 OFF No analogue control ON Analogue control DIP switch 4 OFF Pressure mode ON Vacuum mode DIP switch block 2 with 2 switches DIP switch 1 DIP switch 2 Analogue input 1 OFF OFF 0 ...

Page 7: ...with the continuously lit red LED Table of possible error messages Display Malfunction Short circuit Overvoltage Intermediate circuit Undervoltage Intermediate circuit Overtemperature motor Mains interruption Offset current sensor Overtemperature Power output stage Overcurrent Inner temperature too high Charge relay defective I2 t limitation Earth fault Feldbus timeout IO controller defective RS48...

Page 8: ...m installation altitude Up to 1000 m above sea level without loss of performance Weight kg 5 6 Type of protection IP 55 Maximum cross section power supply mm2 2 5 Maximum cross section pilot wires mm2 1 5 Maximum connection cross section external ventilator mm2 2 5 Terminal range power cable mm 7 0 13 width across flats 25 Terminal range pilot wires mm 4 5 9 0 width across flats 20 Certifications ...

Reviews: