8
VAU4/3
Output voltage, External ventilator supply
[V]
3 AC mains voltage
Fuse, external ventilator supply (optional)
surge-proof 500 mA (T)
Maximum switch-on frequency per hour
12
Digital inputs
Signal level, high status
Signal level, low status
12 V – 30 V
0 V – 5 V
Analogue inputs, Transduction accuracy
10 bit
Analogue outputs
maximum ampacity as current output
maximum apparent ohmic resistance
as current output
10 mA
1 kOhm
24 V DC fixed voltage output
maximum ampacity
70 mA
10 V DC fixed voltage output
maximum ampacity
30 mA
Potential-free contacts, max. load
230 V/2 A
Ventilation
air cooled by motor ventilator
Ambient temperature during operation
°C
0 – 50
Storage temperature
°C
-20 … 70
Maximum humidity
90% without condensation
Maximum installation altitude
Up to 1000 m above sea level without
loss of performance
Weight
[kg]
5.6
Type of protection
IP 55
Maximum cross-section power supply
mm
2
2.5
Maximum cross-section pilot wires
mm
2
1.5
Maximum connection cross-section
external ventilator
mm
2
2,5
Terminal range, power cable:
mm
7.0 … 13, width across flats 25
Terminal range, pilot wires:
mm
4.5 … 9.0, width across flats 20
Certifications
European EMC guidelines
If the VAU4/3 frequency converter is installed and operated according to the recommendations
of these operating instructions, it fulfils all requirements of the EMC regulations according to
the EMC product standards for motor driven systems EN 61800-3.
UR certification
(Use in North America)
“Suitable for use on a circuit capable of delivering not more than 5000 rms sym-
metrical amperes, 380…480Volts (three phase)” and “when protected by J class
fuses.” as indicated.“
The VAU4/3 frequency converter is equipped with a motor overload protector.