Operating Instructions
Control
Checking the running direction
Insert.the.CEE.plug.into.the.CEE.socket.or.switch.on.the.main.switch..Now.use.the.UP.and.DOWN.buttons.to.check.whether.
the.running.direction.of.the.door.agrees.with.these.commands.
Also.observe.the.direction.LEDs.on.the.motherboard.of.the.S50 II.
If the running direction does not correspond to the arrow direction:
Remove.the.CEE.plug,.or.switch.the.main.switch.off..Swap.the.L1.and.L.connections,.for.example,.at.the.mains.connection.
terminals.(see.connection.plan)..Resume.installation.
Setting the end limits
The.control.is.set.at.the.factory.so.that.ascent.is.carried.out.in.self-locking.mode.and.descent.in.deadman’s.mode..To.facilitate.
moving.to.the.fi.nal.position.when.setting.the.limit.switches,.you.can.switch.the.ascent.from.self-locking.to.deadman’s.mode.
with.function.switch.FS2.on.the.“Deadman’s”.control.card..If.the.“Multicard.II”.is.used,.switch.to.the.setting.mode.with.DIP.
switch.8.(“OFF”.position)..Ascent.and.descent.will.then.be.carried.out.solely.in.deadman’s.mode.
Lower end limit setting
Move.the.door.to.the.bottom.end.limit.with.the.DOWN.button.(deadman’s.mode)..Approach.the.desired.end.limit.for.the.door.
by.“tapping”.if.necessary..Set.the.limit.switch.cam.for.DOWN.(black).according.to.the.operating.instructions.for.the.direct.
mount.drive.used.
Upper end limit setting
Move.the.door.to.the.top.end.limit.with.the.UP.button.(deadman’s.mode)..Once.again,.approach.the.desired.top.end.limit.of.
the.door.by.“tapping”.if.necessary..Set.the.limit.switch.cam.for.UP.(grey).according.to.the.operating.instructions.for.the.direct.
mount.drive.used.
Setting the safety limit switches
The.safety.limit.switches.(yellow).are.set.with.approx..°.delay.to.the.respective.operating.limit.switch..Observe.the.relevant.
information.in.the.operating.instructions.for.the.direct.mount.drive..If.a.safety.limit.switch.is.contacted,.the.control.voltage.is.
switched.off..The.relevant.control.cam.must.then.be.turned.away.manually.from.the.limit.switching.micro.switch,.or.cleared.
by.manual.activation.(e.g..crank).
Setting the function switch for pneumatic testing/electrical function cutoff
Function.switch.S7.(orange)
•. Set.the.control.cam.so.that.it.is.activated.max..5.cm.above.the.ground.
•. In.the.case.of.a.pneumatic.edge,.this.setting.serves.for.the.“introduction.of.testing”.in.accordance.with.EN.1245.
•. In.the.case.of.an.electrical.edge,.this.setting.serves.for.“switching.rail.cutoff”,.so.that.no.ascent.or.release.of.the.door.oc-
curs.upon.contact.with.the.ground.
Setting the function switch for partial opening
Function.switch.S8.(green)
•. If.the.setting.of.FS1=B,.this.limit.switch.switches.the.potential-free.relay.of.the.S50II.(see.also.the.description.“Potential-
free.relay”).
•. If.the.setting.of.FS1=A,.this.limit.switch.serves.as.“upper.limit.position”.when.partial.opening.is.activated.(also.see.the.
operating.instructions.“Multicard.II”)
Note
On principle, the precise adjustment of the limit positions is carried out with the fi ne adjustment screw of
the respective control cam (please see also the operating instructions for the door drive).
Commissioning of the system