What to do if...?
Problem
Remedy
Tubular drive does not move.
Program new transmitter.
Bring transmitter within range of the tubular drive.
Check electrical connection.
Thermal protection switch in tubular drive has tripped. Wait until
the thermal protection switch in the tubular drive is reactivated.
Running direction on tubular drive cannot be set.
Delete limit positions (see chapter Deleting limit positions) and
reset the running direction.
Incorrect running direction after deleting limit positions.
Use ReCom or the direction switch on the tubular drive to
change the direction of rotation.
Tubular drive stops arbitrarily; cannot be restarted in the same
direction.
Tubular drive has detected an increase in load. Briefly run the
curtain in the opposite direction, then continue in the desired
direction.
Tubular drive is overloaded. Use a higher-torque tubular drive.
Delete limit positions, then reprogram limit positions.
During the programming run, the drive stops short of the limit
position to be programmed.
For safety reasons, the drive reacts sensitively to sluggishness
during the programming run, in order to prevent damage.
Briefly run curtain DOWN and subsequently UP until you reach
the upper limit position.
Ventilation slots of the roller shutter do not close fully.
Delete the limit positions (see Deleting limit positions) and then
set the limit positions as per "to lower point" (see chapter Set-
ting the limit positions); in this case, set the lower limit position
first (lower point) followed by the upper limit position.
Forgotten security code.
Press the “Delete transmitter” button on the Becker universal
programming unit (item no. 4935 000 001 0) for 10 seconds to
reset the security code to the factory setting.