GENERAL SPECIFICATIONS
Actuator Power
120 V ac, single-phase, 50 or 60 Hz
Allowable Tolerance
+10% / -15%
Max. Current & Power
1.2A, 144W @ 120 V ac
Output Thrust and Timing
1,000 lbs (4 450 N), 4.2 sec/in (1.65 sec/mm)
Stroke Range
5 to 18 inches (127 to 457 mm)
Weight
Approx. 71 lbs (32.2 kg), depending on selected options.
Operating Conditions
–40° to 85° C. (–40° to 185° F.)
0 to 99% relative humidity
Control Options
Three types of control are available:
1) Open/close option 3. Two position control using manual
pushbuttons or an automatic controller.
2) Direct ac control option 5. Actuator is energized by 120 V ac
line current from a remote controller or manual switches.
3) Modulating analog control option 7. Onboard actuator control
electronics position output proportionally to mA Demand input
signal.
Demand Input Signal
4–20 mA or 1–5 V dc
(Option 7)
Deadband
1.0% of Span
Minimum Step
.25% of Span
Hysteresis
.5% of Span at any point
Position Feedback Signal 4–20 mA or 1–5 V dc
(Options 5 & 7)
Feedback may be configured as a two wire transmitter or as a four wire active signal source.
Two wire systems require a customer supplied external power supply. Four wire systems
require 120 V ac supply to the drive.
Isolation
Demand input and position Feedback signals are isolated from
ground and the ac power line. Signal buffering provides 24 V dc
isolation between the signals.
Action on Loss of Power
Stays in place.