Beck 42-103 Instruction Manual Download Page 18

18

80-0042-00, Rev. 06.9

travel, the input signal should be 12 milliamps (3 

volts) and at fully retracted, 4 milliamps (1 volt). 

  Split  signal  operation  is  also  possible. The 

control  board  can  be  adjusted  to  produce  full 

actuator  travel  with  50%  of  the  input  signal, 

permitting two actuators to respond independently 

from the same signal source. Split signal ranges 

are:

   

  4 to 12 milliamps (1 to 3 volts)

   

12 to 20 milliamps (3 to 5 volts)

  It  is  also  possible  to  calibrate  the  control 

board to give a span anywhere between 8 and 16 

milliamps (2 to 4 volts), with the minimum signal 

between 4 and 12 milliamps (1 to 3 volts).  The 

maximum input signal may be anywhere between 

12 and 20 milliamps (3 to 5 volts) as long as the 

span is at least 8 milliamps (2 volts).

  Tools required for calibration: 

   

mA/V dc voltmeter 

   

3/32 inch screwdriver 

   

Large screwdriver

  Table 1 lists the meter connections required for 

the calibration procedure.

  The  calibration  procedure  requires  setting 

two  trim  potentiometers  R13  and  R14  on  the 

control  board.    Figure  7  shows  the  location  of 

these potentiometers and the Manual/Automatic 

switches.

  1. Remove the control module cover.

  2. Set  the  Manual/Automatic  toggle  switch  to 

AUTOMATIC.

  3. Connect a signal source to terminals 11 and 

12, positive to 12.

  4. Connect  the  meter  to  read  the  feedback 

signal in accordance with Table 1, page 16.

Option 5 Control Board

Figure 6

FEEDBACK

POTENTIOMETER

1

1

CCW

CW

P4

P4

R38

R46

1

J6

J5

J5 / J6

Feedback Signal Calibration, cont'd

 15. Position the actuator output shaft to the end 

of travel limit that corresponds to 20 mA (i.e., 

to  the  fully  extended  position  if  the  actuator 

travel  is  set  to  extend  on  an  increasing 

demand  signal,  or  to  the  fully  retracted 

position if the travel is set to retract).  Allow 

the over-travel limit switch to de-energize the 

motor at the limit.

 16. Turn trim potentiometer R38 counterclockwise 

until  the  output  signal  is  20.05  mA  ±  .001 

mA  (5  volts  on  units  configured  for  voltage 

output).

 17. Repeat steps 15 through 16 until the feedback 

signal is calibrated.  Adjusting R38 and R46 

clockwise increases the signal while counter-

clockwise decreases the signal.

 18. Reinstall resistor between terminals 13 and 14 

(if used). 

NOTE:  The input signal is calibrated relative 

to the feedback signal. Therefore the shaft 

travel limit switches must be properly 

adjusted and the feedback signal calibrated 

before the input signal can be calibrated.

DEMAND INPUT SIGNAL CALIBRATION 

(Option 7 only)

NOTE (Option 7):  All actuators are fully 

calibrated at the factory and should require 

no adjustment; however, if necessary, 

calibration may be tested as follows:

  Apply 4.00 mA; actuator should position 

at 4.00 mA ± .02 mA.

 

Apply 20.00 mA; actuator should position 

at 20.00 mA ± .02 mA.

If adjustments are required, see below.

  Input signal calibration is necessary to ensure 

that the input signal correctly corresponds to the 

position of the actuator output shaft. 

  Unless  otherwise  specified  at  the  time  of 

order, all Group 42 actuators are shipped with the 

input signal calibrated for full output shaft travel 

and the input signal range set to 4 to 20 milliamps. 

A 1 to 5 volt input signal may be specified at time 

of  order  or  changed  at  installation. To  convert 

a 4 -20 milliamp  input configuration  to 1-5 volts, 

remove input resistor R1 from the terminal board. 

To convert a 1-5 volt input configuration to 4-20 

milliamps,  install  a  249  ohm  resistor  in  position 

R1. See Figure 5, page 16 for the location of R1.

  When properly adjusted, the actuator output 

shaft will be in the fully extended position when 

the input signal is 20 milliamps (5 volts). At 50% 

CALIBRATION

Summary of Contents for 42-103

Page 1: ...80 0042 00 Rev 06 9 INSTRUCTION MANUAL 42 107 42 105 42 103 MODELS R E L E C T R I C A C T U A T O R S F O R I N D U S T R I A L P R O C E S S C O N T R O L...

Page 2: ...ns 11 Calibration 12 Travel Limit Switch Adjustment 12 Setting Auxiliary Switches 14 Changing Direction of Travel 15 Feedback Signal 16 Demand Input Signal 18 Loss of Signal Function 19 Deadband Adjus...

Page 3: ...ntenance Ideally suited for harsh industrial environments the Group 42 handles long stroke applications requiring up to 1 000 lbs 4 450 N of thrust The design employs a highly efficient ball screw cou...

Page 4: ...ne current from a remote controller or manual switches 3 Modulating analog control option 7 Onboard actuator control electronics position output proportionally to mA Demand input signal Demand Input S...

Page 5: ...adjustable Rated 10 A 125 150 Vac 5 A 125 Vdc 25 A 150 Vdc Handswitch Option 7 Permits local electrical operation independent of Demand input signal Handwheel Provides manual operation without electr...

Page 6: ...7 11 279 28 19 32 726 46 19 32 1183 69 31 2 17 32 DIA 64 7 25 32 198 8 7 32 209 ALLOW 2 3 4 70 FOR REMOVAL 2 1 4 57 3 11 32 85 L DIMENSION 3 8 10 1 1 16 27 SEE TABLE REAR CLEVIS HOLE DIAMETER 1 25 SEE...

Page 7: ...n conductive conduit and or cable trays All signal and power connections are made on the terminal board Typical wiring connections for each Group 42 control option are described on the following pages...

Page 8: ...nal 12 The loop powered position feedback signal must be connected to a 2 wire type analog input that provides a dc voltage over the signal wires a dc voltage power supply must be wired in series with...

Page 9: ...d to terminal 15 Direct AC Control with Actuator Powered Position Feedback Signal Customer must supply three wires to directly control the actuator motor direction One 120 V ac line to run Extend term...

Page 10: ...m2 is recommended for this purpose CONDUIT ENTRIES Conduits are provided for power and signal wiring Temporary plugs are installed in the conduits at the factory for shipping only and are not intended...

Page 11: ...put shaft travels through its desired stroke Note that the F extend and R retract LEDs on the control board light to indicate the direction of travel of the output shaft The LEDs remain lit when the u...

Page 12: ...ine voltage and auxiliary switches are disconnected from external power sources Setting the Retract Travel Limit Switch S3 1 Remove the control module cover 2 Retract the output shaft to the desired t...

Page 13: ...witch wires remove the two wires from the extend limit switch top switch and attach the meter across these contacts See Fig 3 at right Rotate the cam see Fig 2 at right until the meter shows no contin...

Page 14: ...eter and actuator power 8 Extend Retract the output shaft again to the desired switch position If the contacts close the switch is properly set 9 Replace the control module cover SETTING AUXILIARY SWI...

Page 15: ...to the power transformer see Figure 4 this page 3 For extend output shaft travel on an increasing signal the orange wire must be on the common terminal of S4 and the brown wire on the common terminal...

Page 16: ...n TABLE 1 below FEEDBACK SIGNAL CALIBRATION For 4 wire feedback only All Group 42 actuators are shipped with the Option 7 Terminal Board Figure 5 TABLE 1 R4 F1 R3 VR2 VR1 TB1 TB2 22 4001 13 R 2 1 2 1...

Page 17: ...put 14 Move the output shaft towards the maximum input signal position with a 249 ohm resistor To convert a 1 5 volt configuration to 4 20 milliamps remove the 249 ohm resistor and replace it with a 1...

Page 18: ...sition if the travel is set to retract Allow the over travel limit switch to de energize the motor at the limit 16 Turn trim potentiometer R38 counterclockwise until the output signal is 20 05 mA 001...

Page 19: ...n function in two ways 1 Actuator will stay in its last position when the signal was lost 2 Actuator will move to a position determined by the setting of trim potentiometer R16 The LOS function will s...

Page 20: ...to stall will be decreased to 68 seconds which may be shorter than the full stroke travel time of some actuators R20 Parallel Resistor Effective Resistance Dead band 1 000 000 1 0 1 000 000 2 000 000...

Page 21: ...he factory see back cover for factory contact information CUSTOMER KIT PART NUMBER Capacitor Replacement 6 0Nm 72 RPM Motor 60Hz 12 8064 10 Capacitor Replacement 6 0Nm 72 RPM Motor 50Hz 12 8064 20 Res...

Page 22: ...itch failure a b c d Check control board calibration See calibration procedure p 18 Readjust limit switches See limit switch adjustment p 12 Restore input signal to actuator Replace limit switch Conta...

Page 23: ...laims damages costs or liabilities including but not limited to attorney s fees and other legal expenses whether on account of negligence or otherwise except those claims based solely upon the neglige...

Page 24: ...02 19 11 TERRY DRIVE NEWTOWN PENNSYLVANIA 18940 USA PHONE 215 968 4600 FAX 215 860 6383 E MAIL sales haroldbeck com www haroldbeck com HAROLD BECK SONS INC R Made in USA...

Reviews: