8
Technical data
8.1
Reference conditions and limitations
Reference conditions
Relative inlet pressure
mbar(e)
-125
Relative inlet pressure
psi
-1.813
Atmospheric pressure
mbar (a)
1013
Atmospheric pressure
psi (a)
14.69
Air inlet temperature
˚C
20
Air inlet temperature
˚F
68
Exhaust back pressure
mbar(e)
0
Exhaust back pressure
psi
0
Ambient temperature
°C
20
Ambient temperature
°F
68
Limitations
Maximum atmospheric pressure
mbar(a)
1040
Maximum atmospheric pressure
psi(a)
15.08
Minimum atmospheric pressure
mbar(a)
800
Minimum atmospheric pressure
psi(a)
11.61
Maximum ambient temperature
°C
40
Maximum ambient temperature
°F
104
Minimum ambient temperature
°C
1
Minimum ambient temperature
°F
33.8
Maximum inlet temperature
˚C
40
Maximum inlet temperature
˚F
104
Minimum inlet temperature
˚C
1
Minimum inlet temperature
˚F
33.8
Maximum inlet pressure
mbar(e)
0
Maximum inlet pressure
psi(e)
0
Minimum inlet pressure (except AGS 2210)
mbar(e)
-200
Minimum inlet pressure (except AGS 2210)
psi(e)
-2.90
Minimum inlet pressure (AGS 2210)
mbar(e)
-180
Minimum inlet pressure (AGS 2210)
psi(e)
-2.61
Maximum exhaust back pressure
mbar
10
Maximum exhaust back pressure
psi
0.145
Instruction book
38
Summary of Contents for AGS 1560
Page 2: ......
Page 11: ...Simplified schematic of a AGS Simplex installation Instruction book 9...
Page 13: ...AGS Simplex AGS Duplex Instruction book 11...
Page 16: ...Service diagram AGS Simplex 1 ph typical Instruction book 14...
Page 46: ......
Page 47: ......
Page 48: ......