Page 19 of 24
8.6
Acknowledging “Assist Call” alarms
When an “Assist Call” goes into alarm, the appropriate zone LED will flash blue, and a two-tone buzzer
sounds to indicate that an “Assist Call” alarm has been operated.
To acknowledge the alarm, press the corresponding zone button, and the blue LED will illuminate
continuously with an intermittent buzzer tone every 15 seconds. If after 2 minutes the “Assist Call”
alarm has not been cancelled, the buzzer will resound and the LED will flash blue.
Within the WC cubicle the pull cord indicator will change from continuous indication to no indication.
The cancel plate will alter from flashing to continuous and the buzzer will change from continuous to
intermittent. Outside the cubicle the Over door plate indication will alter from flashing to continuous and
the buzzer will change from continuous to intermittent. This change in indication and buzzers during the
acknowledge phase indicates to the WC user that help is on the way.
8.7
Accepting Faults
Before accepting faults, the fault must be noted in the log book, along with the time the fault was
reported.
To accept the fault, enter either the access level 2 (code: 1664) or access level 3 (code: 1812) menu,
then press zone button 1. The buzzer will silence and the general fault LED will now go steady.
Press zone button 8 to exit this menu and to return to the menu options.
The buzzer will resound on each new fault.
8.8
Panel Indicator Test
To test the panel indicators, enter either the access level 2 (code: 1664) or access level 3 (code: 1812)
menu, then press zone button 2.
All LEDs will illuminate in a predefined sequence, and the buzzer will sound.
Press zone button 8 to stop the panel indicator test and to return to the menu options.
9.
Indications and Controls
9.1
Mode Indicator Summary
Mode
Description
Green solid
Normal state
Red solid
Outstation off hook
Blue solid
Assist call active
Yellow Solid
Refuge (type B) points disabled
Flashing Red/Blue
Incoming call/ Assist Call alarm at same time