Install 1 or 2 virtual push buttons as activation zone(s) to open the door «manually».
Apply the vitual push button sticker(s)
within
the optional
field.
Launch a VPB teach-in to configure the detection zone(s).
When the red LED flashes very slowly after 3 seconds, hold
your hand in front of the sticker to learn the detection zone.
The green LED flashes 3x to confirm the selection.
When the red LED flashes again, learn a second (max. 2)
detection zone or wait until the LED switches to green.
Launch a new VPB teach-in each time the sensor position
is changed or new objects are added to or changed in the
detection zone.
ATTENTION! This VPB teach-in is different from the
safety field teach-in.
3 s
In order to configure the field dimensions, you have to cancel the virtual push button function by
launching a new VPB teach-in without any movement in the detection field.
Test the good functioning of the installation before leaving the premises.
FACTORY VALUES
OPTIONAL FIELD CONFIGURATION (RELAY 1)
WIDTH
HEIGHT
FIELD DIMENSIONS
VIRTUAL PUSH BUTTON TEACH-IN (VPB)
Make sure the white and green wires are connected to the corresponding inputs before configuring the
optional field.
Reduce the field dimensons if needed.
Change output configuration to suitable
applications. see page 9.