TROUBLESHOOTING

No blue LED

Only the blue LED is 

on.

The detection LED 

remains green.

The orange LED is 

flashing and the 

detection LEDs are 

red. 

The detection LED 

remains red.

The orange LED 

is on.

The sensor does 

not respond to the 

remote control.

The sensor does not 

unlock.

There is no power.

The test input is not 

connected.

The detection field is too 

small or deactivated.

Someone or something is 

in the detection field.

The field is touching the 

floor, the wall, the door, an 

object or a person which 

leads to detection.

No background (reference 

point) is found.

The sensor is masked.

The power supply voltage is 

exceeding the acceptable 

limits.

The sensor exceeds its 

temperature limits.

Internal error

30 minutes after last use of 

the remote control, the 

sensor locks the access to 

the remote control session.

The batteries in the remote 

control are not installed 

properly or dead.

The remote control is badly 

pointed. 

A reflective object is in close 

proximity to the sensor.

You have to enter an access 

code or the wrong code was 

entered. 

The object size is too small.

The polarity of the power 

supply is inverted.

Check cable and connexion.

Check wiring.

The BLUE and BLUE/WHITE cable have to be 

connected to the test input or the power supply.

Check the size of the fields.
Launch a teach-in.

Step out of the field and/or remove the any 

object(s) from the field and launch a teach in.

Activate the 3 red beams and check if the 

position of the sensor is correct. 

If not, adjust the hex screws.
Verify the field size.
Launch a teach-in.

Check the position of the sensor.

Check the mounting side setting.

If there is no background, set the mounting side 

to value 3 to 5.

Launch a new teach-in.

Verify and clean the front screens 

with a damp cloth.

Check the power supply voltage.

Verify the outside temperature where the sensor 

is installed. Eventually protect the sensor from 

sunlight using a cover.

Wait a few seconds. 

If the LED remains ON, reset the power supply. 

If the LED turns on again, replace the sensor.

Cut and restore power supply. 

The remote control session is accessible again 

during 30 minutes. 

Verify or replace the batteries.

Point the remote control towards the sensor, but 

with a slight angle. The RC should not be 

pointed in a right angle in front of the sensor.

Avoid highly reflective material in proximity to 

the sensor.

Cut and restore power supply. 

No code is required to unlock during the first 

minute after powering.

Check the polarity of the power supply.

Decrease the min. object size.

All LEDs have been de-

activated by remote control.

Activate the LEDs by remote control.

Summary of Contents for LZR-I30

Page 1: ...75 5667 10 LZR I30 20161212 Page 1 of 12 LZR I30 75 5667 10 LZR I30 20161212 Page 1 of 12 EN max detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS ...

Page 2: ...sensor The installer of the door system is responsible for carrying out a risk assessment and installing the sensor and the door system in compliance with applicable national and international regulations and standards on door safety and if applicable the machinery directive 2006 42 EC Other use of the device is outside the permitted purpose and can not be guaranteed by the manufacturer The manufa...

Page 3: ...eption 3 LED signals 4 4 screws for position lock 2 5 connector 6 protection cover 7 visible laser beams 3 8 notches for tilt angle adjustment 2 9 adjustable bracket 10 cable conduits 4 1 Detection LED relay 1 optional field 2 Detection LED relay 2 safety field 3 Error LED 4 Power LED Remote control sequence Possible remote control adjustments Factory values According to Not according to LED flash...

Page 4: ...AMETERS CHECKING A VALUE RESTORING TO FACTORY VALUES SAVING AN ACCESS CODE DELETING AN ACCESS CODE The access code is recommended for sensors installed close to each other After unlocking the red LED flashes and the sensor can be adjusted by remote control If the red LED flashes quickly after unlocking you need to enter an access code from 1 to 4 digits field width 13 7 ft field width is defined b...

Page 5: ... an opening is not possible use the cable conduits on the back side of the bracket Position the bracket and fasten the 4 screws firmly in order to avoid vibrations Position the housing on the bracket and turn the sensor until the two triangles are face to face MOUNTING WIRING POWER SUPPLY RELAY 1 OPTIONAL FIELD RELAY 2 SAFETY FIELD TEST NOT USED RED BLACK WHITE GREEN WHITE BLACK GREEN WHITE BLUE B...

Page 6: ...ion Unlock the sensor and activate the visible laser beams in order to position the curtains parallell to the door POSITIONING The distance between the inner curtains of the 2 sensors shall not exceed 8 in to ensure safety according to EN ISO 13849 1 2008 CAT 2 Pl d After setting the mounting side the safety and the optional field have the same dimensions The visible laser beams stay activated for...

Page 7: ...ing teach in the sensor learns and adapts its detection field shape according to its surroundings During teach in the sensor learns its surroundings and adapts the detection field shape to these Objects in the detection field will be cut out WIDTH HEIGHT no field Ex for a field width of 62 in FIELD DIMENSIONS SAFETY FIELD TEACH IN After the teach in the field dimensions can be changed by the remot...

Page 8: ...r wait until the LED switches to green Launch a new VPB teach in each time the sensor position is changed or new objects are added to or changed in the detection zone ATTENTION This VPB teach in is different from the safety field teach in 3 s In order to configure the field dimensions you have to cancel the virtual push button function by launching a new VPB teach in without any movement in the de...

Page 9: ...ght and side When mounted on the left the distance between curtain C1 and curtain C4 is approximately 4 in for every 3 25 ft mounting height Example at 200 in the distance between C1 and C4 is 20 in OUTPUT ACTIVATION DELAY approximate values off Ex C1 C2 are active on safety field C3 C4 are active on optional field C1 is active on both fields C2 C3 are active on safety field C4 is inactive CURTAIN...

Page 10: ...e and connexion Check wiring The BLUE and BLUE WHITE cable have to be connected to the test input or the power supply Check the size of the fields Launch a teach in Step out of the field and or remove the any object s from the field and launch a teach in Activate the 3 red beams and check if the position of the sensor is correct If not adjust the hex screws Verify the field size Launch a teach in ...

Page 11: ...3516 0 8 in 118 in 1 4 in 197 in 2 75 in 30 ft 700 mm x 300 mm x 200 mm testbody A according to EN 12445 wavelength 905 nm max output pulse power 75 W CLASS 1 wavelength 650 nm max output CW power 3 mW CLASS 3R 10 35 V DC sensor side to be operated from SELV compatible power supplies only 5 W 1 8 A max 80 ms 35 V 33 ft typ 20 ms max 80 ms output activation delay 2 electronic relays galvanic isolat...

Page 12: ...s of the directives 2006 95 EC 2002 95 EC 2004 108 EC and 2006 42 EC Notified Body for EC inspection 0044 TÜV NORD CERT GmbH Langemarckstr 20 45141 D Essen EC type examination certificate number 44 205 11 392410 002 Angleur May 2011 Jean Pierre Valkenberg Authorized representative and responsible for technical documentation The complete declaration of conformity is available on our website www bea...

Reviews: