75.0062 V2 Mar 2002 [Rev. 3/06/2002] 

DIP SWITCH 
SETTINGS

 

SET-UP 
INSTRUCTIONS

 

COMPANY 
CONTACT

 

 
 
 

 
 
Once all components are properly wired together, power can be applied and the set-up can begin.  Only one 
adjustment is necessary on the LE-21 and that is the hold open time delay for the door when the door is operated 
automatically. This adjustment is in the form of five dip switches located on the right side of the unit, which can be set 
to achieve a 0 to 31 second hold open time delay.  The hold open time delay should be set for the length of time the 
door should remain open once the push plate has been released.  Since the LE-21 provides the hold open time delay, 
the time delay on the operator must be set to minimum. 

 

The LED’s on the LE-21 let the installer know that the LE-21 is in operation.  The RED LED signifies that the push 
plate has been activated and the LE-21 is activating and holding the door open.  The RED LED will light as soon as 
the push plate is activated and remain lit for the hold time preset by the installer (once the push button is released).   
The GREEN LED signifies that the SuperScan’s input to the door control will be accepted.   When the GREEN LED is 
on, the SuperScan is capable of reactivating the door if something is in the swing path of the door.  The GREEN LED 
will shut off as soon as the door position switch sends a closed signal to the LE-21 to tell the LE-21 that the door is 
closed.  Once the door is closed and the GREEN LED is off the LE-21 will ignore the input of the SuperScan until the 
push plate activates the door again.

 

 
 

1.  Use the chart provided below to configure the time delay for the LE-21. By default, the unit is set to 7 seconds. 

Only dipswitches 1 through 5 are used for this function. 

 
 

 

 
 
 
 

 

 
 
 
 
 
 
 
 

 
 

If after troubleshooting a problem, a satisfactory solution cannot be achieved, please call B.E.A., Inc. 
for further assistance during 

Eastern Standard Time at 1-800-523-2462 from 8am - 5pm

.  

For after-hours, call East Coast: 1-866-836-1863 or 1-800-407-4545 / Mid-West: 1-888-308-8843 /  
West Coast: 1-888-419-2564. 

DO NOT leave any problem unresolved.

 If you must wait for the following 

workday to call B.E.A., leave the door inoperable until satisfactory repairs can be made.  

NEVER sacrifice the safe operation of the automatic door or gate for an incomplete solution. 
Web: www.beasensors.com 

 

 

 

 

 

 

 
 

Set the dip switches according to the chart below to 
achieve the desired hold open time delay.  The dip 
switches are configured to send a binary coded input 
to the microprocessor to establish the correct time 
delay. 
 
Dip Switch 1 =    1 second 
Dip Switch 2 =    2 seconds 
Dip Switch 3 =    4 seconds 
Dip Switch 4 =    8 seconds 
Dip Switch 5 =  16 seconds 
Dip Switch 6 =  not used 
Dip Switch 7 =  not used 
Dip Switch 8 =  not used 

time 

delay 

(sec) 

dip 1 

1 sec

 

dip 2 

2 sec

 

dip 3 

4 sec

 

dip 4 

8 sec

 

dip 5 

16 sec

 

time 

delay 

(sec) 

dip 1 

1 sec

  

dip 2 

2 sec

 

dip 3 

4 sec

 

dip 4 

8 sec

 

dip 5 

16 sec

 

on off off off  off 

17 

on off off off  on 

off on off off  off 

18 

off on off off  on 

on on off off  off 

19 

on on off off  on 

off off on off  off 

20 

off off on off  on 

on off on off  off 

21 

on off on off  on 

off on on off  off 

22 

off on on off  on 

on 

on 

on 

off 

off 

23 

on on on off  on 

off off off on  off 

24 

off off off on  on 

on off off on  off 

25 

on off off on  on 

10 

off on off on  off 

26 

off on off on  on 

11 

on on off on  off 

27 

on on off on  on 

12 

off off on on  off 

28 

off off on on  on 

13 

on off on on  off 

29 

on off on on  on 

14 

off on on on  off 

30 

off on on on  on 

15 

on on on on  off 

31 

on on on on  on 

16 

off off off off  on 

 

 

 

 

 

 