BEA IRIS Setup Manual Download Page 7

75.5159.09   20090115

 

7/10 

 

 

Important Programming Notes

 

 
 

 

Door Control Mode 

 
The Door Control Mode is used to simulate a permanent detection, or non-detection, 
and is a useful setting while performing service to the door. 

 

 

Installation Configuration 

 
The Installation Configuration key is used for changing the pulse frequency of the 
sensor for the purpose of reducing chances of cross-talk between sensors.  To 
prevent crosstalk when installing overlapping units set one unit to 5 and the other to 
7 for Low Mount or one unit to 6 and the other to 8 for High Mount. 
 

 

Sensor Output 

 
When launching a sensor setup, the sensor may or may not cause a door opening 
cycle. This is because the output from the sensor may be tied to the safety circuit of 
the door controller, which is typically disabled at the closed door position. For a quick 
setup, this is OK. For an assisted setup, the installer must launch the setup, then 
active the door to the open position immediately thereafter. A normal setup routine 
will then follow. 

 

 

Lock Key 

 

Always be sure to press the LOCK key twice, following any programming of the 
sensor. If the LOCK key is not pressed twice, the changes will not be permanently 
stored in the memory. 

 

 

Rain Mode 

 
Rain Mode: When the infrared immunity level is set to Rain Mode, a specific trigger is 
required to enter into the mode: If the sensor completes 2 learn cycles within 6 
detections, it will enter into Rain Mode. During this mode, the sensor will change the 
2

nd

 infrared curtain (the one farthest from the door) to IR motion (as opposed to IR 

presence). This will last for 1 hour, or until power is reset, or until a new setup is 
launched, whichever occurs first. 

 

 

Snow Mode 

 
Snow Mode: When the infrared immunity level is set to Snow Mode, a specific trigger 
is required to enter into the mode: If the sensor completes 2 learn cycles within 6 
detections, it will enter into Snow Mode. During this mode, the sensor will change the 
2

nd

 infrared curtain (the one farthest from the door) to IR motion (as opposed to IR 

presence). Additionally, the automatic learn time will change from whatever it was set 
to, to 10 seconds. This will last for 1 hour, or until power is reset, or until a new setup 
is launched, whichever occurs first. If Snow Mode is selected, additional beams or 
sensors may be required to maintain compliance with applicable safety standards. 

 

 
 

 
 

 

Manual Setup Of The Sensor

 

 

 Manual Setup Procedures 

 

 

 

 

1. 

Set-up of the IRIS may be accomplished by the use of two IRIS mounted programming buttons. The 
procedures below indicate how to program using these buttons. 

2. 

The two setup buttons are located at the right side of the IRIS (as viewed when mounted to header). To 
begin, briefly press the right button and move away from the sensing patterns. 

TO RESET THE UNIT TO FACTORY DEFAULTS: 

 

Press and hold both buttons simultaneously until both red and green LED lights flash alternately 

 

TO CUSTOMIZE SETTINGS FROM FACTORY DEFAULTS 

 

To enter the customizing mode:  Press the right button until the LED light flashes and then release 

 

To return to standard mode:  Press the right button again until the LED light stops flashing and then release

 

 
CUSTOMIZING MODE 

 

The red LED light indicates the number for the function being altered ( 1 flash = function #1) 

 

The green LED light indicates the value for the function being altered ( 1 flash  means value = 1) 

 

The right button enables selection of the function number being altered (+1 for each press) 

 

The left button enables alteration (change in value) of the function  (+1 for each press) 

 

See the chart below for the function assignments: 

 

An Orange LED will be displayed for those functions not utilized. 

 

Summary of Contents for IRIS

Page 1: ...elay Configuration By default it is set to Active value 4 the IRIS relay contact closes upon detection If passive is required change the output configuration value to 1 The most obvious indication to this condition is that the door works in reverse order no detection results in hold open Pulse Frequency If an interference is suspected from other nearby sensors or IR equipment change the frequency ...

Page 2: ... 8 oz Housing material ABS LURAN S Minimum length of cable 10 3 m 9 conductor 10IRIS 30 9 m 9 conductor 10IRIS I Range of Remote Control 16 PRESENCE SENSOR Detection mode Presence Response time 128ms Technology Focused active infrared and self monitored microprocessor Spot diameter standard 4 max Number of spots 24 or 12 spots by curtain Number of curtains 2 Detection field 7 Ht Width Depth Wide 6...

Page 3: ...ir may jeopardize personal safety and may expose one to the risk of electrical shock may adversely affect the safe and reliable performance of the product will result in a voided product warranty 2 Mounting the sensor follow the instructions on the enclosed template Mount the sensor at a maximum height of 2 from the bottom line of the door operator Use the mounting template to drill holes and posi...

Page 4: ...e screw clockwise To tilt the curtain out turn the screw counterclockwise Keep a minimum distance of 2 between the door and the first curtain Use the Spotfinder accessory to locate and adjust the position of the curtains When mounting one sensor on each side of the door above a highly reflective threshold select different frequencies to avoid crosstalk between the sensors 1 Important User Guide Sy...

Page 5: ... will once again be required unless it is deleted as described below To re lock the sensor without a lock code or with a new lock code perform the following To return to no lock code simply press lock once followed by 0000 3 Remote Control Programming Launch a setup by performing the following Unlock the sensor to enter into adjustment session RED LED Press Unlock key flashes slowly To launch an a...

Page 6: ...door permanently open red LED ON 3 door permanently closed red LED OFF No monitoring reply Installation Configuration Mounting Height Pulse Frequency SINGLE UNIT 1 Low Low 2 High Low 3 Low High 4 High High OVERLAPPING UNITS 5 Low Low 6 High Low 7 Low High 8 High High Important Note Upon detection at the sensor both relays will be simultaneous triggered Relay 1 is assigned to the white and green ou...

Page 7: ...ty level is set to Snow Mode a specific trigger is required to enter into the mode If the sensor completes 2 learn cycles within 6 detections it will enter into Snow Mode During this mode the sensor will change the 2 nd infrared curtain the one farthest from the door to IR motion as opposed to IR presence Additionally the automatic learn time will change from whatever it was set to to 10 seconds T...

Page 8: ...mended to set sensors close to each other with remote control The access code can be composed of 1 to 4 digits factory values or no access code 0 or 0000 No code is required to unlock during the first minute after powering To enter a lock code simply press the Lock key followed by a lock code If lock code is less than 4 digits the lock key must be pressed a second time following the last digit of ...

Page 9: ...f the infrared curtains emitted by the IRIS PN 10WCA WCA This is a ceiling adaptor for use on drop ceilings or otherwise Maximum ceiling thickness allowed is about PN 10WMB WMB This is a 90 degree mounting bracket to allow installation on a flat horizontal surface PN 10URC URC This is a universal rain cover to shield the sensor from direct rain contact 6 Accessories sold individually ...

Page 10: ...counterclockwise The door is not closing LED OFF On Off switch at door control is in wrong position or is faulty Check to insure that On Off switch for door is in the ON or AUTOMATIC position Improper output configuration on the sensor Check the output configuration setting on each sensor Improper door control configuration Verify that Door Control F2 is set to Normal The presence detection is dis...

Reviews: