75.5367.08 UL MAGLOCKS 1200lb 20210806  

Page 4 of 5

The product must be powered from a UL-listed, regulated, power-limited, power supply.

12 VDC INPUT

 - Required power:  0.5 AMP / 12 VDC
 - Connect positive (+) lead from a 12 VDC power source to Terminal 1.
 - Connect negative (-) lead from a 12 VDC power source to Terminal 2.
 - Check jumper for 12 VDC operation.

24 VDC INPUT

 - Required power:  0.25 AMP / 24 VDC
 - Connect positive (+) lead from a 24 VDC power source to Terminal 1.
 - Connect negative (-) lead from a 24 VDC power source to Terminal 2.
 - Check jumper for 24 VDC operation.

POWER

If power switch is not wired between DC source v) and magnet, it will take a longer time to de-energize the magnet simulating 

residual magnetism.

Page 2 of 2 

 

 

 

 

 

 

 

 

 

75.5366.02   20140401

5   Installation - Mechanical & Electrical

LOCK ST

ATUS SWITCH (SPDT)

POWER 

SUPPL

Y  

     +    -

POWER

SELECT

OR

JUMPER

LED

MAG BOND SENSOR

MAGNET

TIMER (0-90 SEC)

TYPICAL INSTALLATION

NOTE:  DO NOT over-tighten the armature plate.  The rubber washer is designed to allow the armature 

plate to automatically adjust position for best mating position between the lock and armature plate.

DOOR FRAME

ARMATURE PLATE

MAGNET

ANGLE

BRACKET

MOUNTING

PLATE

MOUNTING

PLATE

STRINGER

HOLE FOR

GUIDE PIN
HOLE FOR NUT

RUBBER WASHER
STEEL WASHER
ARMATURE PLATE

SCREW M8 (35MM)

GUIDE PIN

DOOR

NUT

SPACER

WASHER

ARMATURE

PLATE

DOOR

NUT

DOOR FRAME

DOOR FRAME

DOOR

ARMATURE PLATE

ARMATURE PLATE

MAGNET

MAGNET

DOOR

DOOR

MOUNTING

PLATE

CAUTION:  Observe proper 

circuit board orientation!

NOTE:  The product must be powered from a UL listed, regulated, power limited, power supply.
NOTE:  If power switch is not wired between DC source voltage and magnet,

             it will take a longer time to de-energize the magnet simulating residual magnetism.

1. 12 VDC INPUT
  

A.   Required power 0.5A (Max).
B.   Connect ground (-) lead from a 12 VDC power source to Terminal 2.
C.   Connect positive (+) lead from a 12 VDC power source to Terminal 1.
D.   Check jumper for 12 VDC operation.

2. 24 VDC INPUT

A.   Required power 0.25A (Max).
B.   Connect ground (-) lead from a 24 VDC power source to Terminal 2.
C.   Connect positive (+) lead from a 24 VDC power source to Terminal 1.
D.   Check jumper for 24 VDC operation.

3. CONTACTS

1.   Relay dry contacts are rated 1A at 24 VDC for safe operation, DO NOT exceed this 

rating.

2.   If a NO switch is required, connect the wires from the system to Terminal 4 & Terminal 3.
3.   If a NC switch is required, connect the wires from the system to Terminal 4 & Terminal 5.

DS VERSION

24/7 Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462 | General Tech Questions: [email protected] | Tech Docs: www.beasensors.com

7   Installation 

 Electrical (cont.)

Summary of Contents for 10MAGLOCK1UL

Page 1: ...each Dimensions 10 47 x 2 87 x 1 58 in 266 x 73 x 40 mm 20 94 x 2 87 x 1 58 in 532 x 73 x 40 mm Certification UL1034 UL294 UL1034 UL294 Operating Temperature 32 120 F 0 49 C 32 120 F 0 49 C Operating Humidity 0 85 0 85 UL 294 Performance Ratings required per Chapter 10 of 2015 IBC Destructive Level I Line Security Level I Endurance Level IV Standby Power Level I Static Strength 1000 lb Dynamic Str...

Page 2: ... wear and misalignment 5 You must only use the template with the door in its normally closed position 5 Add threadlocker to all screws before installing and firmly tighten screws 5 Install only for indoor dry applications 5 Installation and wiring must be performed in compliance with ANSI NFPA 70 NFPA 101 CSA C22 1 Canadian Electrical Code Part I safety standard for electrical installations sectio...

Page 3: ...er 5 steel washer 6 armature plate 7 permanent magnet 8 guide pin Align the black plastic piece of the armature plate with the cover plate i e magnet must line up with the switch DOOR SIDE VIEW armature plate nut rubber washer timer LED bond sensor power selector jumper magnet 12 VDC 24 VDC power supply green N O N C COM black red dry contact lock status switch CIRCUIT BOARD NOTE Terminals ratings...

Page 4: ...NET ANGLE BRACKET MOUNTING PLATE MOUNTING PLATE STRINGER HOLE FOR GUIDE PIN HOLE FOR NUT RUBBER WASHER STEEL WASHER ARMATURE PLATE SCREW M8 35MM GUIDE PIN DOOR NUT SPACER ARMATURE PLATE DOOR NUT DOOR FRAME DOOR FRAME ARMATURE PLATE ARMATURE PLATE MAGNET MAGNET DOOR DOOR MOUNTING PLATE CAUTION Observe prop circuit board orientation The product must be powered from a UL listed regulated power limite...

Page 5: ...BLACK LIGHT COM REED SWITCH ON DOOR STATUS SENSOR SWITCH Switch changes state when door is open NO BEA Inc the sensor manufacturer cannot be held responsible for incorrect installations or incorrect adjustments of the sensor device therefore BEA Inc does not guarantee any use of the sensor device outside its intended purpose BEA Inc strongly recommends that installation and service technicians be ...

Reviews: