background image

10MAGDE1 Delayed Egress Electromagnetic Lock

Installation Instructions 

(Continued)

--Specifications

This product has been successfully tested and evaluated by UL in
two separate categories for use in both the United States and
Canada.

Auxiliary Lock. The GWXT fire listing qualifies the 10MAGDE1

for use with UL Classified fire doors maximum 4' in width and 8' in
height, rated up to and including 1-1/2 hr.

Component for use in Special Locking Arrangments.

Additionally, these products are qualified components for the
purpose of locking outward-swinging exit doors against
unauthorized egress.They are designed to release automatically in
case of a power failure or upon activation of an automatic fire
alarm system wired to the power supply fire panel relay.

The Following Conditions of Acceptability Apply: 

1

) This product is intended for use with Special Locking

Arrangements which are installed in accordance with the
manufacturer's installation and operation instructions, the Life
Safety Code, NFPA 101 of the National Fire Protection Association
and the local authority having jurisdiction.

2

) The power for this unit is to be provided by a Listed (ALVY,

FULA7, FUPPC, UEHX7, APHV or APHV7) Class 2 power supply
when designated as a Special Locking Arrangement (FWAX).

3

) The suitability of the lead wires is to be evaluated per the

requirements for the end-use product.

4

) When this component is used in a system designated as a

Special Locking Arrangement (FWAX), it is to be evaluated as part
of the overall system with respect to the requirements in the Life
Safety Code, NFPA 101 for the end-use product.

The Delayed Egress electromagnetic locks are not intended or
tested for use as a UL Listed Burglar Alarm System unit.

Patent Pending

MECHANICAL 

Including 1/4” (6.4mm) mounting bracket

:

10MAGDE1 Lock Dimensions:
2-1/8”D x 2-7/8”H x 10-13/16”L (54mm x 73mm x 275mm)

10MAGDE1 Armature Plate Dimensions:
5/8”D x 2-3/8”H x 7-7/16”L (16mm x 60mm x 189mm)

ELECTRICAL:
Voltage:

Auto Sensing 12VDC to 24VDC 

Power Consumption:

12VDC - Max 0.61A / 24VDC - Max 0.32A

Ratings shown include the external sounder required by NFPA101

Local Alarm Output:

SPDT Relay: 1.0A 120VAC, 2A 30VDC

Remote Alarm Output:

DPDT Relay: 1.0A 120VAC, 2A 30VDC

ENVIRONMENTAL:

Not for use in outdoor environments.
Circuit board operating temperature: -14 to 140˚F (-10 to 60˚C)

NOTE:

The 10MAGDE1 electromagnetic lock must be powered with a

filtered and regulated DC power supply listed to UL294, UL603,  CSA-
C22.2, ULC-S318 or ULC-S533 and rated 12 to 24V. 
BEA recommends model 10PS12-24.
The magnet warranty is 5 years.

Specifications subject to change without notice.

To Ensure Instant Release

All switching devices must be wired in between

the DC power source and the positive terminal of the lock as illustrated 
in Fig 2. 

Switching the negative power supply line will not allow the lock to
release immediately. BEA electromagnetic locks contain MOV's for
surge suppression and do not require any additional suppression to
be added during installation. The installation of diodes across the
lock input terminals will cause a delay in release.

Fig. 2 – Power Connections

SWITCH

+

-

INCORRECT

CORRECT

+

-

SWITCH

FILTERED DC SUPPLY

FILTERED DC SUPPLY

Page 3 of 8

Summary of Contents for 10MAGDE1

Page 1: ...ation Instructions for further information 11 Installation of this product should be done by an experienced installer with knowledge of this product 12 A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 NOTE It is highly recommended that thread locking compound be applied to all screws during installation to reduce chance of screws loosening over extended time...

Page 2: ...ssure is maintained for longer than the set nuisance delay an irreversable release delay sequence begins This release delay is for 15 seconds but may be extended to 30 seconds with permission of the Authority Having Jurisdiction AHJ It includes the short nuisance delay Pressure is no longer required on the door The remote relay de energizes The local buzzer changes from a pulse to steady The lock ...

Page 3: ...e overall system with respect to the requirements in the Life Safety Code NFPA 101 for the end use product The Delayed Egress electromagnetic locks are not intended or tested for use as a UL Listed Burglar Alarm System unit Patent Pending MECHANICAL Including 1 4 6 4mm mounting bracket 10MAGDE1 Lock Dimensions 2 1 8 D x 2 7 8 H x 10 13 16 L 54mm x 73mm x 275mm 10MAGDE1 Armature Plate Dimensions 5 ...

Page 4: ... the door a door switch cannot be used for relocking Please connect a momentary spring loaded NORMALLY OPEN key switch to system Reset Switch Input RST 2 STANDARD BUILDING CODE 1999 NUISANCE DELAY Not allowed RELEASE DELAY 15 sec RELOCK Actuates after door OPENS and CLOSES using a door switch rather than a key switch Please connect a NORMALLY OPEN door switch by others to system Reset Switch Input...

Page 5: ...TACT BEA FOR INFORMATION ON A DELAYED EGRESS WITH BUILT IN CAMERA 10MAGDE1 Delayed Egress Electromagnetic Lock Installation Instructions Continued Wiring Diagram Diagram reflects status with power on and door opened A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 Reset and Override Wiring for BOCA Requirements Diagram reflects status with power on and door ...

Page 6: ...s com US and Canada 1 866 249 7937 Canada 1 866 836 1863 Northeast 1 866 836 1863 Southeast 1 800 407 4545 Midwest 1 888 308 8843 West 1 888 419 2564 10MAGDE1 Delayed Egress Series Troubleshooting Guide PROBLEM SOLUTION Remove anti tamper screw and cavity screw Insert supplied Allen wrench into mounting bolt holes in the bottom of the lock housing and turn See Fig 1 Check power supply DC power sho...

Page 7: ... a lock to be installed Available in several different widths For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock from the frame Available in several different thicknesses For use with doors that do not permit the armature plate to be mounted low enough t...

Page 8: ...14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy o...

Reviews: