background image

10MAGDE1 Delayed Egress Electromagnetic Lock

Installation Instructions 

(Continued)

Total One Way

Length of

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

Wire Run (ft.)

100

24

20

18

18

16

16

14

12

150

22

18

16

16

14

14

12

10

200

20

18

16

14

14

12

12

10

250

18

16

14

14

12

12

12

10

300

18

16

14

12

12

12

10

--

400

18

14

12

12

10

10

--

--

500

16

14

12

10

10

--

--

--

750

14

12

10

10

--

--

--

--

1000

14

10

10

--

--

--

--

--

1500

12

10

--

--

--

--

--

--

Total One Way

Length of

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

Wire Run (ft.)

100

20

18

16

14

14

12

12

10

150

18

16

14

12

12

12

10

--

200

16

14

12

12

10

10

--

--

250

16

14

12

10

10

10

--

--

300

16

12

12

10

10

--

--

--

400

14

12

10

--

--

--

--

--

500

14

10

10

--

--

--

--

--

750

12

10

--

--

--

--

--

--

1000

10

--

--

--

--

--

--

--

1500

10

--

--

--

--

--

--

--

Load Current @24V

Load Current @12V

Wire Gauge Chart courtesy of Electronic Locking Devices by John L. Schum

WIRE GAUGE SELECTIONS

Page 8 of 8

Summary of Contents for 10MAGDE1

Page 1: ...ation Instructions for further information 11 Installation of this product should be done by an experienced installer with knowledge of this product 12 A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 NOTE It is highly recommended that thread locking compound be applied to all screws during installation to reduce chance of screws loosening over extended time...

Page 2: ...ssure is maintained for longer than the set nuisance delay an irreversable release delay sequence begins This release delay is for 15 seconds but may be extended to 30 seconds with permission of the Authority Having Jurisdiction AHJ It includes the short nuisance delay Pressure is no longer required on the door The remote relay de energizes The local buzzer changes from a pulse to steady The lock ...

Page 3: ...e overall system with respect to the requirements in the Life Safety Code NFPA 101 for the end use product The Delayed Egress electromagnetic locks are not intended or tested for use as a UL Listed Burglar Alarm System unit Patent Pending MECHANICAL Including 1 4 6 4mm mounting bracket 10MAGDE1 Lock Dimensions 2 1 8 D x 2 7 8 H x 10 13 16 L 54mm x 73mm x 275mm 10MAGDE1 Armature Plate Dimensions 5 ...

Page 4: ... the door a door switch cannot be used for relocking Please connect a momentary spring loaded NORMALLY OPEN key switch to system Reset Switch Input RST 2 STANDARD BUILDING CODE 1999 NUISANCE DELAY Not allowed RELEASE DELAY 15 sec RELOCK Actuates after door OPENS and CLOSES using a door switch rather than a key switch Please connect a NORMALLY OPEN door switch by others to system Reset Switch Input...

Page 5: ...TACT BEA FOR INFORMATION ON A DELAYED EGRESS WITH BUILT IN CAMERA 10MAGDE1 Delayed Egress Electromagnetic Lock Installation Instructions Continued Wiring Diagram Diagram reflects status with power on and door opened A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 Reset and Override Wiring for BOCA Requirements Diagram reflects status with power on and door ...

Page 6: ...s com US and Canada 1 866 249 7937 Canada 1 866 836 1863 Northeast 1 866 836 1863 Southeast 1 800 407 4545 Midwest 1 888 308 8843 West 1 888 419 2564 10MAGDE1 Delayed Egress Series Troubleshooting Guide PROBLEM SOLUTION Remove anti tamper screw and cavity screw Insert supplied Allen wrench into mounting bolt holes in the bottom of the lock housing and turn See Fig 1 Check power supply DC power sho...

Page 7: ... a lock to be installed Available in several different widths For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock from the frame Available in several different thicknesses For use with doors that do not permit the armature plate to be mounted low enough t...

Page 8: ...14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy o...

Reviews: