background image

10MAGDE1 Delayed Egress Electromagnetic Lock

Installation Instructions 

(Continued)

Delayed Egress System  –  Status Indicators

System Status

Light Panel

Local Buzzer

Local Alarm Relay Remote Alarm Relay

Door Open

Red on

OFF

OFF

OFF

Locked

Green blinks every 

5 seconds

OFF

OFF

ON

Nuisance Delay

Period

Red blinking (fast)

Pulsing Sound

ON

ON

Release Delay

Period

Red blinking (slowly)

Steady Sound

ON

OFF

Lock Release

Red/Green blinking

alternately

Steady Sound

Until Reset

OFF

OFF

Forced Open

Red blinking (fast)**

Pulsing Sound**

ON

OFF

Exit Switch to Open

Red On

OFF

OFF

OFF

Delayed Egress System  –  Overview

The Delayed Egress electromagnetic lock is a fail safe device.

In the normal condition with power, the door is locked, the local
buzzer is off, the local SPDT relay is de-energized and the remote
alarm DPDT relay is energized.

The exit sequence starts with a slight push to the door.  A nuisance
delay period can be set for 0, 1, 2 or 3 seconds as defined by the
local building code.  During this period the local buzzer will pulse
and the local alarm relay will be energized. If pressure on the door
is withdrawn during this period the system returns to normal
conditions.  This would be considered accidental triggering.

If pressure is maintained for longer than the set nuisance delay, an
irreversable release delay sequence begins.  This release delay is
for 15 seconds, but may be extended to 30 seconds with
permission of the Authority Having Jurisdiction (AHJ). It includes
the short nuisance delay.  Pressure is no longer required on the
door.  The remote relay de-energizes.  The local buzzer changes
from a pulse to steady.  

The lock releases when the release delay time ends.  The local
buzzer stops and the local alarm relay will de-energize.  The system
relock is defined by the local building code.

All installations must be approved by the local Authority Having
Jurisdiction (AHJ).

Lock Assembly

The Delayed Egress Electromagnetic Lock come with screws that inhibit
the insertion of an Allen wrench into the mounting bolt openings on the
underside of the lock. These screws will need to be removed prior to
installing the lock so as to allow the mounting plate to be removed from
the top of the lock.  Fig 1 illustrates the location of these screws. 

Fig. 1 – Lock Assembly View

anti-tamper
screw

cavity screw

Several building codes
including the NFPA 101 Life
Safety Code and the
International Building Code
require the signage (shown
left) to be mounted on the
door close to the releasing
device.

Page 2 of 8

** If forced open before the set release delay has lapsed, the sounder and voice indicators can only be turned off by switching
the system power off.

Summary of Contents for 10MAGDE1

Page 1: ...ation Instructions for further information 11 Installation of this product should be done by an experienced installer with knowledge of this product 12 A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 NOTE It is highly recommended that thread locking compound be applied to all screws during installation to reduce chance of screws loosening over extended time...

Page 2: ...ssure is maintained for longer than the set nuisance delay an irreversable release delay sequence begins This release delay is for 15 seconds but may be extended to 30 seconds with permission of the Authority Having Jurisdiction AHJ It includes the short nuisance delay Pressure is no longer required on the door The remote relay de energizes The local buzzer changes from a pulse to steady The lock ...

Page 3: ...e overall system with respect to the requirements in the Life Safety Code NFPA 101 for the end use product The Delayed Egress electromagnetic locks are not intended or tested for use as a UL Listed Burglar Alarm System unit Patent Pending MECHANICAL Including 1 4 6 4mm mounting bracket 10MAGDE1 Lock Dimensions 2 1 8 D x 2 7 8 H x 10 13 16 L 54mm x 73mm x 275mm 10MAGDE1 Armature Plate Dimensions 5 ...

Page 4: ... the door a door switch cannot be used for relocking Please connect a momentary spring loaded NORMALLY OPEN key switch to system Reset Switch Input RST 2 STANDARD BUILDING CODE 1999 NUISANCE DELAY Not allowed RELEASE DELAY 15 sec RELOCK Actuates after door OPENS and CLOSES using a door switch rather than a key switch Please connect a NORMALLY OPEN door switch by others to system Reset Switch Input...

Page 5: ...TACT BEA FOR INFORMATION ON A DELAYED EGRESS WITH BUILT IN CAMERA 10MAGDE1 Delayed Egress Electromagnetic Lock Installation Instructions Continued Wiring Diagram Diagram reflects status with power on and door opened A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 Reset and Override Wiring for BOCA Requirements Diagram reflects status with power on and door ...

Page 6: ...s com US and Canada 1 866 249 7937 Canada 1 866 836 1863 Northeast 1 866 836 1863 Southeast 1 800 407 4545 Midwest 1 888 308 8843 West 1 888 419 2564 10MAGDE1 Delayed Egress Series Troubleshooting Guide PROBLEM SOLUTION Remove anti tamper screw and cavity screw Insert supplied Allen wrench into mounting bolt holes in the bottom of the lock housing and turn See Fig 1 Check power supply DC power sho...

Page 7: ... a lock to be installed Available in several different widths For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock from the frame Available in several different thicknesses For use with doors that do not permit the armature plate to be mounted low enough t...

Page 8: ...14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy o...

Reviews: