Operating Manual 

Industrial pressure transmitter DMK / DMP,  
screw-in transmitter LMK / LMP and 
OEM pressure transmitter 

DMK 331, DMK 331 P, DMK 351, DMK 351 P, DMP 311, 
DMP 320, DMP 321, DMP 331, DMP 331i, DMP 331 P,  
DMP 331 Pi, DMP 333, DMP 333i, DMP 334, DMP 334i, 
DMP 335, DMP 339, DMP 343, LMK 331, LMK 351,  
LMP 331, LMP 331i,  
17.6XX, 17.6XX G, 18.6XX, 18.6XX G, 
26.6XX, 26.6XX G, 30.6XX, 30.6XX G 

Headquarters 

BD SENSORS GmbH 
BD-Sensors-Str. 1 
D - 95199 Thierstein 
Germany 
Tel.: +49 (0) 9235-9811-0 
Fax: +49 (0) 9235-9811-11 

Eastern Europe 

BD SENSORS s.r.o. 
Hradištská 817 
CZ - 687 08 Buchlovice 
Czech Republic 
Tel.: +42 (0) 572-4110 11 
Fax: +42 (0) 572-4114 97 

Russia  

BD SENSORS RUS 
39a, Varshavskoe shosse 
RU - Moscow 117105 
 
Russia 
Tel.: +7 (0) 95-380 1683 
Fax: +7 (0) 95-380 1681 

China  

BD SENSORS China Co, Ltd. 
Room B, 2nd Floor, Building 10, 
No. 1188 Lianhang Rd. 
201112 Shanghai,  
China 
Tel.: +86 (0) 21-51600 190 
Fax: +86 (0) 21-33600 613 

The  addresses  of  our  distribution  partners  are  listed  on  our 
homepage  www.bdsensors.com.  It  is  possible  to  download 
data  sheets,  operating  manuals,  ordering  codes  and  certifi-
cates, as well. 

1. General information 

1.1 Information on the operating manual 

This  operating  manual  contains  important  information  on 
proper usage of the device. Read this operating manual care-
fully before installing and starting  up the  pressure measuring 
device. 

Adhere  to  the  safety  notes  and  operating  instructions  which 
are given in the operating manual. Additionally applicable reg-
ulations regarding occupational safety, accident prevention as 
well  as  national  installation  standards  and  engineering  rules 
must be complied with! 

This operating manual is part of the device, must be kept near-
est its location, always accessible to all employees. 

– Technical modifications reserved – 

1.2 Symbols used 

 

DANGER!  –  dangerous  situation,  which  may  result  in 
death or serious injuries 

 

WARNING! – potentially dangerous situation, which may 
result in death or serious injuries 

 

CAUTION! – potentially dangerous situation, which may 
result in minor injuries 

!

 

CAUTION! – potentially dangerous situation, which  may 
result in physical damage  

 

NOTE  –  tips  and  information  to  ensure  a  failure-free 
operation 

1.3 Target group 

 

WARNING!  To  avoid  operator  hazards  and  damages  of 
the  device,  the  following  instructions  have  to  be  worked 
out by qualified technical personnel. 

1.4 Limitation of liability 

 

By non-observance of the operating manual, inappropri-
ate  use, modification or damage,  no liability is assumed 
and warranty claims will be excluded. 

 

1.5 Intended use 

-  The  pressure  transmitter  DMK/DMP  and  OEM-pres-

sure transmitter have, according to the type, been devel-
oped for applications in overpressure and vacuum as well 
as  for  absolute  pressure  measurement.  The  screw-in 
transmitters LMK/LMP
 have been particularly developed 
for level and process measurement. It is the operator's re-
sponsibility to check and verify the suitability of the device 
for the intended application. If any doubts remain, please 
contact  our  sales  department  in  order  to  ensure  proper 
usage. BD SENSORS is not liable for any incorrect selec-
tions and their effects! 

!

 

Permissible  media  are  gases  or liquids,  which  are  com-
patible with the media wetted parts described in the data 
sheet. In addition it has to be ensured, that this medium 
is compatible with the media wetted parts.  

!

 

The technical data listed in the current data sheet are en-
gaging. If the data sheet is not available, please order or 
download it from our homepage. 

 

(http://www.bdsensors.com) 

 

WARNING! Danger through improper usage!  

1.6 Package contents 

Please  verify  that  all  listed  parts  are  undamaged  included  in 
the delivery and check for consistency specified in your order: 

-  pressure transmitter or screw-in transmitter 

-  for mechanical pressure ports DIN 3852: o-ring  

(pre-assembled) 

-  mounting instructions 

-  with option SIL2 version:  

Functional Safety Manual, Functional Safety Data 
Sheet

 

1.7 UL – Approval (for devices with UL-identification) 

The UL – Approval was done with respect to U.S. standards 
norms  which  also  correspond  with  the  applicable  Canadian 
standards norms for safety. 

Note the following points, so that devices fulfils the demands 
of UL approval: 

-  The transmitter shall be supplied by Limited Energy 

Source (per UL 61010) or NEC Class 2 Power Source. 

-  maximum operating voltage: see technical data 

2. Product identification 

The device can be identified by its manufacturing label. It pro-
vides the most important data. By the ordering code the prod-
uct can be clearly identified. 

 

!

 

The  manufacturing  label  must  not  be  removed  from  the 
device! 

3. Mechanical installation 

3.1 Mounting and safety instructions 

 

WARNING!  Install  the  device  only  when  depressurized 
and currentless! 

 

WARNING! This device may only be installed by qualified 
technical personnel who has read and understood the op-
erating manual! 

Oxygen 

 

DANGER! When used improperly, special versions of de-
vices  suitable  for  oxygen  applications  may  explode!  To 
ensure a usage without danger, the following points must 
be adhered to: 

-  Make sure that your device  has been ordered as a 

special  version  for  oxygen  applications  and  that  it 
has been delivered conformably. You can check this 
easily by reading the manufacturing label (see figure 
1).  If  your  ordering  code  ends  with  the  numbers 
"007", your device is suitable for the oxygen applica-
tion. 

-  When being dispatched the device is packed into a 

plastic  bag  to  keep  it  from  impurity.  The  indication 
label  with  the  text  "Device  for  oxygen,  unpack  only 
directly before assembling" has to be observed! Fur-
thermore  any  skin  contact  must  be  avoided  during 
unpacking and installing the device, so that no fatty 
residue remains on the device! 

-  For installing the respective regulations for explosion 

protection  have  to  be  fulfilled.  Please  check  if  an 
ATEX-approval  is  necessary  for  the  application  in 
addition  to  the  acceptability  for  oxygen.  (the  deliv-
ered device has no ATEX-approval) 

-  Consider  that  the  entire  construction  must  corre-

spond to the standards of BAM (DIN 19247). 

-  For  oxygen  applications  over  25 bar  are  recom-

mended pressure transmitter without seals. 

-  Transmitters  with  o-rings  of  70  EPDM  281: 

permissible  maximum  values:  15  bar/  60°  C  and  
10 bar/ 60 up to 90°C. 

-  Transmitters  with  o-rings  of  FKM  Vi  567: 

permissible maximum values: 15 bar/ 60° C. 

!

 

Handle this high-sensitive electronic precision measuring 
device with care, both in packed and unpacked condition! 

!

 

There  are  no  modifications/changes  to  be  made  on  the 
device.  

!

 

Do not throw the package/device! 

!

 

To  avoid  damaging  the  diaphragm,  remove  packaging 
and protective cap directly before starting assembly. The 
delivered protective cap has to be stored! 

!

 

Place  the  protective  cap  on  the  pressure  port  again 
immediately after disassembling. 

!

 

Handle  the  unprotected  diaphragm  very  carefully  -  it  is 
very sensitive and may be easily damaged. 

!

 

Do not use any force when installing the device to prevent 
damage of the device and the plant! 

!

 

For  installations  outdoor  and  in  damp  areas  following 
these instructions: 

-  To prevent moisture admission in the plug the device 

should  be  installed  electrically  after  mounting,  at 
once.  Otherwise  a  moisture  admission  has  to  be 
blocked e.g. by using a suitable protection cap. (The 
ingress  protection  in  the  data  sheet  is  valid  for  the 
connected device.)  

-  Choose an assembly position, which allows the flow-

off of splashed water and condensation.  Avoid per-
manent fluid at sealing surfaces! 

-  When using a cable gland or outlet device, turn the 

outgoing  cable  downwards.  If  the  cable  has  to  be 
turned upwards, then point it downward so the mois-
ture can drain. 

-  Install  the  device  in  such  a  way  that  it  is  protected 

from  direct  solar  irradiation.  Direct  solar  irradiation 
can  lead  to  the  permissible  operating  temperature 
being overstepped in the worst case. By this the op-
erability of the device can be affected or damaged. If 
the internal pressure increases due to solar irradia-
tion, measurement errors may be caused. 

!

 

For  devices  with  gauge  reference  in  the  housing  (small 
hole next to the electrical connection), install the device in 
such  a  way,  that  the  gauge  reference  is  protected  from 
dirt and moisture. Should the device be exposed to fluid 
admission, the functionality will be blocked by the gauge 
reference. An exact measurement in this condition is not 
possible.  Furthermore  this  can  lead  to  damages  on  the 
device. 

 

Take note that no inadmissibly high mechanical stresses 
occur at the pressure port as a result of  the installation, 
since this may cause a shifting of the characteristic curve 
or  to  the  demage.  This  is  especially  important  for  very 
small  pressure  ranges  as  well  as  for  devices  with  a 
pressure port made of plastic. 

 

In  hydraulic  systems,  position  the  device  in  such  a  way 
that the pressure port points upward (ventilation). 

 

Provide  a  cooling  line  when  using  the  device  in  steam 
piping. 

 

If  there  is  any  danger  of  damage  by  lightning  or 
overpressure  when  the  device  is  installed  outdoor,  we 
suggest  putting  a  sufficiently  dimensioned  overpressure 
protection between the supply or switch cabinet and the 
device. 

 

If the device is installed with the pressure connection up, 
it has to be made sure that no liquid drain off at the case. 
Humidity and dirt can block the relative cover in the case 
and it could lead to malfunctions  through this. Dust and 
dirt must be removed from the edge of the thread connec-
tion of the electrical connection if required. 

3.2 General installation steps 

-  Carefully remove the pressure measuring device from the 

package and dispose of the package properly. 

-  Go ahead as detailed in the specific instructions below.  

3.3 Installation steps for DIN 3852 

 

DO  NOT  USE  ANY  ADDITIONAL  SEALING  MATERI-
ALS, LIKE YARN, HEMP OR TEFLON TAPE! 

-  Check to ensure the proper groove fitting of the o-ring and 

additionally to ensure no damage to the o-ring. 

-  Ensure that the sealing surface of the taking part is per-

fectly smooth and clean. (R

3.2) 

-  Screw the device into the corresponding thread by hand. 

-  If  you  have  a  device  with  a  knurled  ring,  the  transmitter 

has to be screwed in by hand only. 

-  Devices with a spanner flat have to be tightened with an 

open-end wrench (wrench size of steel: G1/4": approx. 5 
Nm; G1/2": approx. 10 Nm; G3/4": approx. 15 Nm; G1": 
approx. 20 Nm; G1 1/2": approx. 25 Nm;  wrench size of 
plastic: max. 3 Nm). 

-  The  indicated  tightening  torques  must  not  be  

exceeded! 

Fig. 1 manufacturing label- example 

DMP 331 

DMP 331P 

74-06 

 

Ordering code 

Connector pinout 

Type 

designation 

Supply 

Nominal 

pressure 

range 

Signal 

Serial 

number 