BA_DMU-ES_OEM_E_22.08.2017 

3.4 Installation steps for EN 837 

-  Use a suitable seal, corresponding to the medium and the 

pressure input (e. g. a cooper gasket). 

-  Ensure that the sealing surface of the taking part is per-

fectly smooth and clean. (R

6.3) 

-  Screw the device into the corresponding thread by hand. 

-  Tighten  it  with  a  wrench  (for  G1/4":  approx.  20  Nm;  for 

G1/2": approx. 50 Nm). 

-  The indicated tightening torques must not be  

exceeded! 

-  Note: permitted pressure ranges according to 

 

EN 837! 

for G1/4“ and G1/2“ according to EN837: 

G1/4“ 
EN837 

P

 600 bar 

Counterpart has to be 
of steel according to 
DIN17440 with stren-
gth 
Rp0,2 

 190 Nmm2 

G1/2“ 
EN837 

P

 1000 bar 

G1/4“ 
EN837 

P

> 600 bar,  

P

 1000 bar 

Counterpart has to be 
of steel according to 
DIN17440 with stren-
gth   
Rp0,2 

 260 Nmm2  

G1/2“ 
EN837 

P

> 1000 bar, 

P

 1600 bar 

3.5 Installation steps for NPT  

-  Use a suitable seal (e. g. a PTFE-strip). 

-  Screw the device into the corresponding thread by hand. 

-  Tighten it with a wrench (for 1/4" NPT: approx. 30 Nm; for 

1/2" NPT: approx. 70 Nm). 

-  The indicated tightening torques must not be  

exceeded! 

3.6 Installation steps for flare 

-  Cut  the  end  at  right  angle  to  the  piping  and  remove  all 

internal and external burrs. 

-  Make the flare; depending on the usage, the device has 

to be tightened with max. 10 Nm. 

-  The indicated tightening torques must not be  

exceeded! 

3.7 Installation steps for internal threads M20x1.5 and 

9/16" UNF (for DMP 334) 

-  Screw  the  high  pressure  connection  into  the  internal 

thread of the DMP 334 and tighten it properly with approx. 
160 Nm. 

 

DANGER! The high pressure tube seals metal-to-
metal in the chamfer of the pressure port. No fur-
ther seal is allowed with this high pressure con-
nection.  A  wrong  installation  can  cause  enor-
mous danger! 

3.8 Installation steps for dairy pipe 

-  Check to ensure that the O-ring fits properly into the in-

tended groove in the mounting part. 

-  Center the dairy pipe connection in the counterpart. 

-  Screw the cup nut onto the mounting part. 

-  Then tighten it with a hook wrench. 

3.9 Installation steps for Clamp and Varivent

 

-  Use a suitable seal corresponding to the medium and the 

pressure input.  

-  Put the seal onto the corresponding mounting part. 

-  Center  the  Clamp  or  Varivent

  connection  on  the  fitting 

counterpart with seal. 

-  Then fit the device with a suitable fastening element (e. g. 

semi-ring or retractable ring clamp) according to the sup-
plier’s instructions. 

3.10 Installation steps for connecting flanges 

-  Use a suitable seal corresponding to the medium and 

pressure input. (e. g. a fiber gasket). 

-  Put the seal between connecting flange and counter 

flange. 

-  Install the device with 4 resp. 8 screws (depending on 

flange version) on the counter flange. 

4. Electrical Installation 

 

WARNING!  Install  the  device  in  currentless  condition 
only! 

Establish the electrical connection of the  device according to 
the  technical  data  shown  on  the  manufacturing  label,  the 
following table and the respective wiring diagram. 

Pin configuration: 
Wiring diagrams: 

2-wire-system (current) 

3-wire-system (current/supply) 

!

 

For devices with cable gland as well as cable socket, you 
have to make sure that the external diameter of the used 
cable is within the allowed clamping range. Moreover you 
have  to  ensure  that  it  lies  in  the  cable  gland  firmly  and 
cleftlessly! 

!

 

For the installation of a device with cable outlet following 
bending radiuses have to be complied with: 

cable without ventilation tube: 

 

  static installation : 

5-fold cable diameter 

 

  dynamic application:  10-fold cable diameter 

 

cable with ventilation tube: 

 

  static installation : 

10-fold cable diameter 

 

  dynamic application:  20-fold cable diameter 

!

 

Please note for devices with ISO 4400 or Buccaneer plug, 
that  the  cable  socket  has  to  be  mounted  properly  to 
ensure  the  ingress  protection  mentioned  in  the  data 
sheet.  Please  check  if  the  delivered  seal  is  placed 
between  plug  and  cable  socket.  After  connecting  the 
cable fasten the cable socket on the device by using the 
screw. 

!

 

On  devices  with  field  housings,  the  terminal  clamps  are 
situated  under  the  metal  cap.  To  install  the  device 
electrically, the cap must be screwed off. Before the cover 
is screwed on again, the O-ring and the sealing surface 
on  the  housing  have  to  be  checked  for  damages  and  if 
necessary to be changed! Afterwards screw the metal cap 
on by hand and make sure that the field housing is firmly 
locked again. 

!

 

Prevent the damage or removal of the PTFE filter which 
is fixed over the end of the air tube on devices with cable 
outlet and integrated air tube. 

 

For  the  electrical  connection  a  shielded  and  twisted 
multicore cable is recommended. 

 

If  a  transition  is  desired  from  a  transmitter  cable  with 
gauge tube to a cable without gauge tube, we recommend 
our terminal box KL 1 or KL 2. 

5. Initial start-up 

 

WARNING!  Before  start-up,  the  user  has  to  check  for 
proper installation and for any visible defects. 

 

WARNING!  The  device  can  be  started  and  operated  by 
authorized  personnel  only,  who  have  read  and  under-
stood the operating manual! 

 

WARNING! The device has to be used within the tech-
nical specifications, only! (compare the data in the data 
sheet) 

 

The  transmitter  shall  be  supplied  by  Limited  Energy 
Source (per UL 61010) or NEC Class 2 Power Source. 

 

Devices  with  an  accuracy  of  0.1  %  FSO  have  micro-
controlled  electronics  for  processing  and  improving  the 
signal. Principally, the processing takes more time as for 
analogue sensors, which  have only an amplifier. Due to 
this  longer  response  time,  the  output  signal  follows  the 
measured  value  discontinuously.  For  nearly  stable 
measured values, this characteristic is secondary. Please 
compare the specification of the response time in the data 
sheet. 

 

Intelligent 

devices 

with 

optional 

communication  

interfaces  can  also  be  configured  by  these  electronics. 
Offset,  span  and  damping  are  programmable  within  the 
limits given in the data sheet. For configuring the device, 
the programming kit CIS 510 consisting of Adapt 1, Win-
dows

 

compatible 

programming 

software  

P-Scale 510, power supply and connecting cable is nec-
essary.  This  can  be  ordered  additionally  from  BD SEN-
SORS. 

6. Placing out of service 

 

WARNING!  Disassemble  the  device  only  in  current  and 
pressure less condition! Check before disassembly, if it is 
necessary to drained off the media before dismantling! 

 

WARNING! Depending on the medium, it may cause dan-
ger for the user. Comply therefore with adequate precau-
tions for purification. 

7. Maintenance 

In  principle,  this  device  is  maintenance-free.  If  desired,  the 
housing of the device can be cleaned using a damp cloth and 
non-aggressive cleaning solutions, in switched-off state. 

With certain media, however, the diaphragm may be polluted 
or  coated  with  deposit.  It  is  recommended  to  define  corre-
sponding service intervals for control. After placing the device 
out of service correctly, the diaphragm can usually be cleaned 
carefully  with  a  non-aggressive  cleaning  solution  and  a  soft 
brush  or  sponge.  If  the  diaphragm  is  calcified,  it  is  recom-
mended to send the device to BD SENSORS for decalcifica-
tion. Please note the chapter “Service/Repair” below. 

!

 

A  false  cleaning  of  the  device  can  cause  an  irreparable 
damage on the diaphragm. Therefore never use pointed 
objects or pressured air for cleaning the diaphragm. 

8. Service / Repair 

8.1Recalibration 

During  the  life-time  of  a  transmitter,  the  value  of  offset  and 
span may shift. As a consequence, a deviating signal value in 
reference to the nominal pressure range starting point or end 
point may be transmitted. If one of these two phenomena oc-
curs  after  prolonged  use,  a  recalibration  is  recommended  to 
ensure furthermore high accuracy. 

8.2 Return 

Before  every  return  of  your  device,  whether  for  recalibration, 
decalcification,  modifications  or  repair,  it  has  to  be  cleaned 
carefully and packed shatter-proofed.  You  have to enclose a 
notice of return with detailed defect description when sending 
the  device.  If  your  device  came  in  contact  with  harmful 
substances,  a  declaration  of  decontamination  is  additionally 
required.  Appropriate  forms  can  be  downloaded  from  our 
homepage  www.bdsensors.com.  Should  you  dispatch  a 
device  without  a  declaration  of  decontamination  and  if  there 
are any doubts in our service department regarding the used 
medium,  repair  will  not  be  started  until  an  acceptable 
declaration is sent. 

 

If  the  device  came  in  contact  with  hazardous 
substances,  certain  precautions  have  to  be 
complied with for purification! 

9. Disposal 

The device has to be disposed of according to the 
European 

Directives 

2002/96/EG 

and 

2003/108/EG  (on  waste  electrical  and  electronic 
equipment). It is prohibited to place electrical and 
electronic equipment in domestic refuse! 

 

WARNING! Depending on the used medium, deposit on 
the device may cause danger for the  user and the envi-
ronment. Comply with adequate precautions for purifica-
tion and dispose of it properly. 

10. Warranty conditions 

The warranty conditions are subject to the legal warranty pe-
riod of 24 months from the date of delivery. In case of improper 
use, modifications of or damages to the device, we do not ac-
cept  warranty  claims.  Damaged  diaphragms  will  also  not  be 
accepted.  Furthermore,  defects  due  to  normal  wear  are  not 
subject to warranty services. 

11. Declaration of conformity / CE 

The 

delivered 

device 

fulfils 

all  legal 

requirements.  

The applied directives, harmonised standards and documents 
are listed in the EC declaration of conformity, which is available 
online at: http://www.bdsensors.com. 
Additionally, the operational safety is confirmed by the CE sign 
on the manufacturing label.  

 

Electrical 

connections 

ISO 4400 

 

Binder 723 

(5-pin) 

Binder 723 

(7-pin) 

M12x1 / 

metal 

(4-pin) 

field-hou-

sing 

cable-col-

ours 

DIN47100 

Buccaneer 

(4-pin) 

TRIM TRIO

(4-pin) 

 
supply 

 

 (only for 3-wire) 









IN + 
IN – 

OUT + 

wh (white) 

bn (brown) 

gn (green) 





 

shield 

ground pin 

 

ye/gn (yel-

low / 

green) 

communication- 

RxD 

interface 

TxD 

GND 

















digital signal 

 

RS485 

GND 

 

pin A 

 

pin B 
















wh (white) 

bn (brown) 
ye (yellow) 

pk (pink) 





 

shield 

pressure 

port 

 

ye/gn (yel-

low / 

green) 

 / in + 

 

supply – / in - 

 

V

S

 

 

 / in + 

 / out 

V

S

 

A

 

/

 

I/U 

supply – / in - 