PM5-REL-4 Relay Module – User Manual
4
5.
Now insert the aluminium rail at its original position.
Take care that the PM5-REL-4 plug-in module is
exactly located in the corresponding slot of the
aluminium rail as shown on the second photo below.
6.
Remount the lid of the connection terminal box and
close the controller casing.
7.
After completion and verification of the installation
you can reconnect mains power supply to the
PoolManager
®
controller.
6
Menu Configuration
The relay switch outputs OUT5..OUT8 can flexibly be
assigned to various add-on functions of the
PoolManager
®
in the same way as the internal standard
relay switch outputs.
The assignment is done in the Menus of the individual
add-on functions, e.g.
Switch output 1..4
,
Filter pump
or
Heating
. In den Menus for the individual add-on functions
there is always a sub-menu called
Basic configuration
. In
this sub-menu, the used relay switch outputs can be
assigned, amongst others.
The figure shows an example of a menu for the
assignment of a relay switch output.
The relay switch outputs of the PM5-REL-4 plug-in
module
are
named
OUT5[REL4],
OUT6[REL4],
OUT7[REL4] and OUT8[REL4] in the menu.
Relay switch outputs which have already been assigned,
are greyed out and cannot be selected anymore. If no
PM5-REL-4 module is plugged-in, all of the outputs
OUT5..OUT8 are greyed out and cannot be selected.
For further details, please refer to the description of the
individual add-on functions in the PoolManager
®
-user
manual.
7
Technical Data
Max. switching voltage AC~
230V~
Max. switching voltage DC=
30V=
Max. switching current AC~/ DC=
3A~/3A=
Max. switching cycles
ca. 20.000 at 3A
OUT 5 / OUT 6
Changeover switches
OUT 7 / OUT 8
On/off switches
•
All relay switch contacts are volts-free.
Hazard!
No electrical circuit protection
There is no internal fuse or other electrical
circuit protection for the relay switch outputs.
Potential consequence: Damage or
destruction of connected devices, risk of
fire.
•
Provide an appropriate external fuse or
other electrical circuit protection.