PM5-REL-4 Relay Module – User Manual

 

4

 

5.

 

Now insert the aluminium rail at its original position. 
Take care that the PM5-REL-4 plug-in module is 
exactly located in the corresponding slot of the 
aluminium rail as shown on the second photo below. 

 

 

 

 

 

6.

 

Remount the lid of the connection terminal box and 
close the controller casing. 

7.

 

After completion and verification of the installation 
you can reconnect mains power supply to the 
PoolManager

®

 controller. 

6

 

Menu Configuration 

The  relay  switch  outputs  OUT5..OUT8  can  flexibly  be 
assigned  to  various  add-on  functions  of  the 
PoolManager

®

  in  the  same  way  as  the  internal  standard 

relay switch outputs. 

The  assignment  is  done  in  the  Menus  of  the  individual 
add-on  functions,  e.g. 

Switch  output  1..4

Filter  pump

  or 

Heating

. In den Menus for the individual add-on functions 

there is always a sub-menu called 

Basic configuration

. In 

this  sub-menu,  the  used  relay  switch  outputs  can  be 
assigned, amongst others. 

 

 

 

The  figure  shows  an  example  of  a  menu  for  the 
assignment of a relay switch output. 

The  relay  switch  outputs  of  the  PM5-REL-4  plug-in 
module 

are 

named 

OUT5[REL4], 

OUT6[REL4], 

OUT7[REL4] and OUT8[REL4] in the menu. 

Relay switch outputs which have already been assigned, 
are  greyed  out  and  cannot  be  selected  anymore.  If  no 
PM5-REL-4  module  is  plugged-in,  all  of  the  outputs 
OUT5..OUT8 are greyed out and cannot be selected. 

For  further  details,  please  refer  to  the  description  of  the 
individual  add-on  functions  in  the  PoolManager

®

-user 

manual. 

7

 

Technical Data 

 

Max. switching voltage AC~ 

230V~ 

Max. switching voltage DC= 

30V= 

Max. switching current AC~/ DC= 

3A~/3A= 

Max. switching cycles 

ca. 20.000 at 3A 

OUT 5 / OUT 6 

Changeover switches 

OUT 7 / OUT 8 

On/off switches 

 

 

All relay switch contacts are volts-free. 

 

Hazard! 

No electrical circuit protection 

There  is  no  internal  fuse  or  other  electrical 
circuit protection for the relay switch outputs. 

Potential consequence: Damage or 
destruction of connected devices, risk of 
fire. 

 

Provide  an  appropriate  external  fuse  or 
other electrical circuit protection.

 

 

 