3.3
Water connection diagrams
IMPORTANT: The water connection diagram of each system
should be determined together with the respective regulation
(see the regulation instructions).
3.4
Gas connection
The gas connection will be done on the rear left-hand side
of the boiler.
3.5
Connection to the chimney
- The draught diverter includes a socket collar where the
flue duct will fit and whose dimensions are indicated (see
the chapter «Main Features»).
- Calculation of the flue duct must comply with current
regulations.
- Site the boiler in the boiler room so that the flue duct run
is as short as possible. The vertical section above the
draught diverter should be as long as possible before
fitting a bend. The average chimney «pull» (see diagram)
should not be less than 0.8 mm w.g. or more than 3 mm
w.g. with the boiler in operation.
- The flue duct should be carefully secured and must not be
supported by the boiler. It is advisable to fit a removable-
type flue system.
1 metre minimum
(recommended)
The distance for measuring
the cheminey ‘’pull’’ is equal to
the Ø of the cheminey
Recommended system diagram
Table : calculation of flue ducts for connecting two
identical boilers.
3.6
Room ventilation
The boiler should be installed in a room separate from living
quarters, with direct ventilation to the outside.
Air intake openings should be free of obstacles at all times,
thus allowing for minimum ventilation
Ø colector
Ø conducto de
fumos
Ø ligação
Number
of
sections
Heat Output
in kW for
1 Boiler
Heat Output
in kW for
2 Boilers
Dimensions in mm
Ø of
connection
Ø of
header
Ø of
flue duct
11
166.6
333
252
400
400
14
215.3
430.6
302
400
400
17
265
530
352
450
450
20
314.6
629.2
402
500
500
22
347.8
695.6
402
500
500
Number of
Sections
Heat Output
in kW
Minimum Ventilation
Cross-section (cm²)
11
166.6
775
14
215.3
1005
17
265
1240
20
315.6
1470
22
347.8
1625