50
925.916.2 - GB
InstructIons pertaInInG to the InstaLLer
14.3 vertICal flue termInal Ø 60/100 mm InstallatIon optIons
This type of installation can be carried out both on a flat or pitched roof by fitting a terminal, an appropriate weathering
tile and sleeve, (supplementary fittings supplied on demand).
L max = 10 m
L max = 10 m
L max = 9 m
L max = 8 m
9912221000
… separated flue-air ducting
This type of ducting allows to disengage exhaust flue gases both outside the building and into single flue ducts.
Comburant air may be drawn in at a different site from where the flue terminal is located.
The splitting kit consists of a flue duct adaptor (100/80) and of an air duct adaptor.
For the air duct adaptor fit the screws and seals previously removed from the cap.
011015_0100
flue duct adaptor
Intake air duct adaptor
The 90° bend allows to connect the boiler to flue-air ducting regardless of direction as it can be rotated by 360°. It can
moreover be used as a supplementary bend to be coupled with the duct or with a 45° bend.