8
10777 - GB-CZ-HU-PL-RO-RU - 0 - 04 / 07
- Fit a vacuum gauge (-1 to 0 bar) to the pump vacuum
connector (reference M).
- Fit a U shaped pipe or sloping pipe (0 to 4 mbar) to the
head air pressure connector (reference C).
- Prepare the darkening index (ST), smoke temperature,
and CO
2
measuring equipment as well as the smoke
sampling hole in the smoke flue.
6.4
Air presetting (burner shut down)
Burners are delivered with the following settings that
correspond to the size of nozzle delivered .
One stage burner
Two stage burner
6
START UP
6.1
Preliminary checks
- Check that the burner specifications are absolutely
equivalent to the fuel and boiler specifications.
- Check type of electric current available in the boiler room
(it shall be 230V » + earth).
- Check that the plant is full of water.
- Check oil level in the tank.
- Check that valves are open.
6.2
Pump starting
- Fill the pipes between the tank and burner either by
gravity if there is a filling “Tee”, or by starting the pump.
- Unscrew the pressure connector (reference K), insert a
flexible pipe and start the burner. When the fuel reaches
the pressure connector, stop the burner and screw up
the pressure connector. Avoid running the burner too
long without fuel in order not to damage the pump.
6.3
Fitting the measuring instruments
- Fit a pressure gauge (0 to 15 bar) to the pump pressure
connector (reference K).
One stage burner
Two stage burner
One stage burner
- Head air setting (oil line)
Boiler power setting: using a No. 4 hex head wrench,
turn the setting screw reference L, one way or the
other according to the setting desired.
- Internal air flow setting (regulator)
Boiler power setting: using a No.4 hex head wrench,
turn the setting button reference V, one way or the
other according to the setting desired. Notches on
the button and casing are for locking the button in
position.
- Suction air setting (intake)
Boiler power setting: unscrew the reference U screws,
adjust the intake reference O to the desired
graduation, screw up the reference U screws.
L
V
U
Line reference
6
Regulator reference
15.7
Intake reference
11.5
Pump pressure
11 bar
Line reference
4.5
Servo motor cam
orange
65°
red
100°
black
70°
Intake reference
11.5
Pump pressure
1
st
stage
11 bar
2
nd
stage
21 bar
Typical settings for 12% to 13% CO2:
L
= line reference,
V
= air regulator,
O
= intake
Max height
Reference atmospheric pressure
50 m
1013 mbar
250 m
990 mbar
500 m
960 mbar
750 m
930 mbar
1000 m
905 mbar
2000 m
800 mbar
Boiler
power
(92% output)
kW
Burner heat
output
KW
Oil
flow
Kg / hr
L
V
O
L
V
O
L
V
O
L
V
O
L
V
O
L
V
O
80
87
7.3
2.0 13.3 11.5 2.1 13.7 11.5 2.3 13.7 11.5 2.5 13.7 11.5 2.7 14.0 11.5 3.5 14.3 11.5
90
98
8.2
2.8 14.0 11.5 2.9 14.0 11.5 3.1 14.0 11.5 3.3 14.3 11.5 3.5 14.3 11.5 4.4 15.0 11.5
100
109
9.2
3.4 14.3 11.5 3.5 14.3 11.5 3.7 14.7 11.5 3.9 14.7 11.5 4.0 14.7 11.5 4.4 15.3 11.5
110
120
10.1
3.9 14.7 11.5 4.0 15.0 11.5 4.1 15.0 11.5 4.2 15.0 11.5 4.3 15.3 11.5 4.5 16.0 11.5
120
130
11.0
4.2 15.0 11.5 4.3 15.3 11.5 4.4 15.3 11.5 4.4 15.7 11.5 4.5 15.7 11.5
130
141
11.9
4.4 15.7 11.5 4.5 16.0 11.5 4.5 15.7 11.5
140
152
12.8
4.5 16.0 11.5
Typical settings for 12% to 13% CO2:
L
= line reference,
O
= intake
Max height
Reference atmospheric pressure
50 m
1013 mbar
250 m
990 mbar
500 m
960 mbar
750 m
930 mbar
1000 m
905 mbar
2000 m
800 mbar
Boiler
power
(92% output)
kW
Burner heat
output
KW
Oil
flow
Kg / hr
L
O
L
O
L
O
L
O
L
O
L
O
80
87
7.3
2.0
11.5
2.1
11.5
2.3
11.5
2.5
11.5
2.7
11.5
3.5
11.5
90
98
8.2
2.8
11.5
2.9
11.5
3.1
11.5
3.3
11.5
3.5
11.5
4.0
11.5
100
109
9.2
3.4
11.5
3.5
11.5
3.7
11.5
3.9
11.5
4.0
11.5
4.4
11.5
110
120
10.1
3.9
11.5
4.0
11.5
4.1
11.5
4.2
11.5
4.3
11.5
4.5
11.5
120
130
11.0
4.2
11.5
4.3
11.5
4.4
11.5
4.4
11.5
4.5
11.5
130
141
11.9
4.4
11.5
4.5
11.5
4.5
11.5
140
152
12.8
4.5
11.5