Installation – Page 4
PREPARATION
(a)
Where the closure plate is more than adequate in height to
cover the fireplace opening, trim a minimum of 35mm (1
3/8 in) from the top of the closure plate to prevent the
sealing tape being seen above the fire. Where the closure
plate is inadequate to cover the fireplace opening
completely or where it is required for the sake of
appearance a NON-COMBUSTIBLE infill panel or
surround may be used. The infill panel should be provided
with a rectangular opening at least 508mm (20in) high by
305mm (12in) wide and must be securely fixed and sealed
to the wall to prevent air leakage into the flue.
(b)
Fit the closure plate centrally across the fire opening and
seal all four edges but ensure that the ventilation hole at
the bottom of the closure plate is not covered and that the
floor behind the closure plate does not restrict the
ventilation hole.
(c)
Apply a lighted taper, match or smoke match to the flue
spigot opening in the closure plate before fitting the fire. If
there is a definite flow into the opening in the closure plate,
proceed with the installation. If there is not a definite flow
into the opening, pre-heat the chimney for a few minutes
then re-check for the flue pull. If there is still no definite
flow into the flue spigot opening in the closure plate the
chimney may require attention. DO NOT FIT THE FIRE -
SEEK EXPERT ADVICE.
HEARTH FIXING
Fireplace or Surround
(a)
Fit the fire backing plate to the fire using the M5 x 8mm
thread forming screws provided. The backing plate may be
screwed to the wall for extra support if necessary (Fig. 6).
(b)
Position the fire (minus the outer case) against the closure
plate and determine the position of the gas connection.
(c)
Adjust the feet to level the fire (Fig.7). Check that the fire is
sufficiently stable.
WALL FIXING
(a)
Fit the two wall mounting brackets using the four No. 8 x
3/8in self tapping screws provided (Fig. 7).
(b)
Fit the fire backing plate to the fire using the M5 x 8mm
thread forming screws provided.(Fig. 6)
(c)
Mark the position of the bottom two fixing screws then drill
and plug the wall (Fig. 4).
(d)
Fix two No. 8 x 1 ½in screws into the wall leaving 3 - 4mm
(1/8 in - 5/32 in) clearance under the screw head then
locate the fire onto the screws.
(e)
Push the fire backwards until the fire backing plate touches
the surround or finished wall face. Mark the position of the
two lower securing holes in the fire backing plate (Fig. 6).
(f)
Remove the fire then drill and plug the wall.
(g)
Replace the fire then screw the fire back to the wall and
tighten all four screws.
CONNECTING THE GAS SUPPLY
Rc ¼ (¼in BSP internal taper).
NOTE: If a hole has to be cut in the closure plate for the gas
supply pipe, seal the opening between the gas pipe and the
closure plate, ensuring that the ventilation hole is kept
clear.
(a)
Make the gas connection to the union elbow.
(b)
Fit the control knob and make sure that the tap is off. (Turn
fully clockwise).
(c)
Turn the gas on, check for gas soundness.