Fuses
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
Baumüller Nürnberg GmbH
266
11.2
11.2 Fuses
A distinction is made between protecting the power supply cables and protecting the de-
vice. To fulfill CE specifications – here in particular EN 60204-1 – fuse the power supply
cables.
Cable protection
Use safety fuses of the operating class gL VDE 0636-201 / DIN EN 60269-2-1 / HD
630.2.1 54 or circuit breaker triggering characteristic K, in accordance with VDE 0636-201
/ DIN EN 60269-2-1 / HD 630.2.1 54, to protect the cable. These fuses protect against
overloads and consequential damage from defects, for example as a result of fire. How-
ever, they cannot prevent a device from being extensively destroyed in case of a short-
circuit or ground fault in the DC link.
Carry out the fusing in accordance with EN 60204-1 („Electrical Equipment of Machines“).
Dimension the cable fuse based on the cross-section of the power supply cable used, and
in accordance with the respective applicable national standards and local regulations.
The current-carrying capacity of the cables is specified in Table 5 of EN 60204-1. For your
application, the corresponding value must still be determined based on the standard itself,
i. e. taking into account the cable routing.
NOTE!
The fuse specification are valid for basic units, only.
NOTE!
Approved, UL-listed safety fuses and/or circuit breakers must be used in UL-autho-
rized systems.
NOTE!
Use suitable fuses with the tripping characteristic gL or gR.
Summary of Contents for b maXX 5500
Page 315: ......