N 153

 

 

 www.baumer.com 

12

 

Example 2: Transmit new profile (new profile number = 17) 

 

SOH 

Adr 

Cmd  Profile no. = 17 EOT 

CRC 

Transmission 

01h 

20h 

56h 

31h 

37h 

04h 

3E 

 

SOH 

Adr 

Cmd  Profile no. = 17 EOT 

CRC 

Response 

01h 

20h 

56h 

31h 

37h 

04h 

3E 

 
Example 3: New profile by broadcast command to all SPAs (identifier = 99 (83h); new profile number = 17) 

 

SOH 

Adr 

Cmd  Profile no. = 17 EOT 

CRC 

Transmission 

01h 

83h 

56h 

31h 

37h 

04h 

04 

 

Response 

Not confirmed 

 

To check whether the new profile has been adopted by all SPAs utilize check command „C“ (43h). 
 
 

4.2.8. Set actual value as preset „Z“ (5Ah) 

 

Command “Z” is utilized to set the actual value at any optional value. The required position value is transmitted 
to the SPA. The SPA will calculate a so-called “preset offset” value relating to the true absolute encoder posi-
tion. When calculating the preset offset, any programmed offset transmitted by command “U” will be considered, 
so that after having accomplished command “Z” the current value always equals the preset. 

 
Note

: If the resolution is altered (see command “a”) from 1/100 to 1/10 or vice-versa, the previously pro-

grammed preset has to be set anew. The auto-calculated offset is provided in the previously selected resolu-
tion. 
 

 

The actual value displayed is composed as follows: 

 

 actual 

value

displz

  =  actual value

abs

  +  preset offset  +  Offset 

Immediately after having accomplished command „Z“ applies preset value = current valuet-

displ

 

Current value

displ  

actual value indicated in the display and read out by interface  

Current value

abs

 

internal absolute actual value (not corresponding to the transmitted preset value). 

Preset offset   

offset generated by command „Z“. 

Offset   

Additional offset enabled by command „U“. This function must be enabled first in command 
bit parameter ‚a’ (61h), otherwise the offset is 0. 

 
Example 1: Read out presently active preset value 

 

SOH  Adr  Cmd  EOT  CRC 

Transmission 

01h  20h  5Ah  04h  38h 

 

SOH  Adr  Cmd 

Preset value = 2.50 

EOT CRC

  Response 

01h  20h  5Ah 

30h  30h  30h

32h

35h

30h

04h

27h

 
Example 2: Set actual value as preset value (preset value = 17.25) 

 

SOH  Adr  Cmd 

Preset value = 17.25 

EOT CRC

  Transmission 

01h  20h  5Ah 

30h  30h  31h

37h

32h

35h

04h

09h 

 

SOH  Adr  Cmd 

Preset value = 17.25 

EOT CRC

  Response 

01h  20h  5Ah 

30h  30h  31h

37h

32h

35h

04h

09h

 
Example 3: Set actual value as preset at all SPAs by broadcast command 

 

SOH  Adr  Cmd 

Preset value = 17.25 

EOT CRC

  Transmission 

01h  83h  5Ah 

30h  30h  31h

37h

32h

35h

04h AAh

 

 

Response 

Not confirmed 

 

Summary of Contents for N153

Page 1: ...etriebsarten 3 2 Terminal assignment 4 3 Interface 4 3 1 Interface data 4 3 2 Protocol 5 3 3 Checksum Cyclic Redundancy Check 5 3 4 Data transmission properties 5 3 5 Broadcast commands 5 3 6 Data saving 6 3 7 Transmitting and reading negative values 6 3 8 Transmitting and reading position values decimal point 6 4 Command explanations 7 4 1 General information 7 4 2 Operating commands 7 4 3 Parame...

Page 2: ... the equipment processes machines to be monitored controlled might lead to fatal injuries serious damage to health damage to property or corporate equipment or damage to the device Any overvoltage the device might be exposed to at its connecting terminals has to be limited to the values stipulated in overvoltage category II see technical data The device must not be operated in hazardous areas wher...

Page 3: ...perator a Direct mode In direct mode the master will transmit the motor start signal command D to a specific SPA which is first to be aligned by power tool The red status LED is flashing fast at approx 2 Hz while the relevant IR positioning data are being transmitted to the power tool After the positioning operation the LED switches to green continu ous what is recognized by the master when readin...

Page 4: ...ngs Abschirmungsanschluss 3 Interface 3 1 Interface data Type RS485 Baudrate 19200 Parity No Data bits 8 Stop bits 1 Handshake No Checksum Yes CRC To avoid bus collisions a minimum timeout reply of 1 ms default parameter is to be kept i e the time elapsed between transmitting the last bit of the query until start transmitting the 1st bit of the SPA response The operator should see that due to the ...

Page 5: ... ever 04H XOR z Add result as CRC after the footer token 04H to the string transmitted Note 1101 0000 RL 1010 0001 Important Bit 7 is shifted in bit 0 during rotation Example Transmitted string less CRC 01h 20h 43h 04h CRC Byte 0Ah 0000 0000 RL 0000 0000 XOR 0000 0001 01h 0000 0001 0000 0001 RL 0000 0010 XOR 0010 0000 20h 0010 0010 0010 0010 RL 0100 0100 XOR 0100 0011 43h 0000 0111 0000 0111 RL 00...

Page 6: ...t of 1 5 and a programmed resolution of 1 10 the transmitted value is 00015 3 8 Transmitting and reading position values decimal point Position values as for example target command S offset command U or end positions command g are generally transmitted and read without decimal point Visualization in the display corresponds to the format in the data field of the interface command Thus the transmiss...

Page 7: ...d actual value S 53h 8 X X X Read write target U 55h 6 X X Offset V 56h 2 X X X X Read write profile number Z 5Ah 6 X X X X Set preset t 74h 6 X Transmit tool number u 75h 6 X Transmit optional column of figures 4 2 1 Check Position C 43h This command provides the alignment status of target versus actual value If the actual value is within the target tolerance window the response will be o 6Fh for...

Page 8: ...art command D is transmitted to the re spective device identifier including group number The status LED is flashing rapidly indicating that the SPA is transmitting motor control data see also examples 1 and 2 Second all SPAs of one group can be started at the same time by broadcast command ID 99 In this case the status LEDs of the SPAs belonging to the respective group are flashing at the frequenc...

Page 9: ... for alignment by power tool however so far there has not been any IR data transmission LED is flashing slowly Motor start is enabled using the key Direct mode motor start signal via device address SPA is enabled for alignment by power tool IR data are being transmitted LED is flashing reserved ever 1 Stat2 1 0 0 0 0 0 0 X 1 Motor is running Moving Bit The bit is set during motor start enable LED ...

Page 10: ...0h 53h 31h 32 30h 30h 31h 32h 35h 30h 04h 3E Response upon clearing all targets SOH Adr Cmd Profile no FFh Target FFFFFFh EOT CRC Response 01h 20h 53h 3Fh 3F 3Fh 3Fh 3Fh 3Fh 3Fh 3Fh 04h 2Ah Example 2 Read specific target profile number 17 target 12 50 SOH Adr Cmd Profile no 17 EOT CRC Transmission 01h 20h 53h 31h 37h 04h 16h SOH Adr Cmd Profile no 17 Target 12 50 EOT CRC Response 01h 20h 53h 31h 3...

Page 11: ...d by adding sub command F to the respective basic command Since it is a pure individual positioning operation defined groups are not affected Collision prevention is up to the operator Example Write specific target utilizing command SPF profile number 17 target 12 50 SOH Adr Cmd Sub1 Sub2 Profile 17 Target 12 50 EOT CRC Transmission 01h 20h 53h 50h 46h 31h 37h 2Dh 30h 31h 32h 35h 30h 04h A0h SOH A...

Page 12: ...e set anew The auto calculated offset is provided in the previously selected resolu tion The actual value displayed is composed as follows actual valuedisplz actual valueabs preset offset Offset Immediately after having accomplished command Z applies preset value current valuet displ Current valuedispl actual value indicated in the display and read out by interface Current valueabs internal absolu...

Page 13: ...as well as both arrows are suppressed The upper line still indicates actual target or the column of figures The column is indicated until any optional command except t u or R is received by the interface The num ber will be retained after power failure Example Column of figures 012345 SOH Adr Cmd Column of figures 012345 EOT CRC Transmission 01h 20h 75h 30h 31h 32h 33h 34h 35h 04h B6h SOH Adr Cmd ...

Page 14: ... Data4 5 0 0 1 1 0 0 0 0 reserved Important Only bits marked X may be altered The permanent parameters 1 and 0 must not be altered since this might create a control token tokens 20h what is not permitted in ASCII protocol Example 1 read bit parameter data1 to data3 80h data4 to data5 30h SOH Adr Cmd EOT CRC Transmission 01h 20h 61h 04h 4E bit parameter default Example 2 write bit parameter positio...

Page 15: ...ctual value target arrow to the left 01 Down As Up but inverted arrows direction 10 Uni If actual value target arrows ever indicated 11 Off Arrows ever hidden Note A loop operation as backlash compensation is only performed with settings Up and Down Uni and Off always implicate a direct movement to the target without backlash compensation Rounding the actual value This means that the actual value ...

Page 16: ...get current value Indicate arrows too if target current value 2 Ever Target and arrows ever suppressed Resolution This parameter defines the resolution of the actual value Upon altering the resolution the decimal point is shifted correspondingly by one digit to the right or left same applies also to actual value and target The target values however are not converted correspondingly but only the de...

Page 17: ...ved Important Only bits marked X may be altered The permanent values 1 and 0 must not be altered since thereby a control token tokens 20h might be created what is not permitted in ASCII Example 1 read bit parameter data 1 to data 3 80h data 4 to data 5 30h SOH Adr Cmd EOT CRC Transmission 01h 20h 6Dh 04h 56h Bit parameter default Example 2 write bit parameter key assignment down motor direction Do...

Page 18: ...PLC or PC may utilize this parameter for general assignments 0 R Shaft type R 1 A Shaft type A Groups Parameter for division in groups Individual SPAs can be bundled to 8 different groups to be started in succes sive order group by group command D in order to prevent collisions 0 group 1 1 group 2 7 group 8 Start command D must comprise the designated group number to start the respective group 4 3...

Page 19: ...e 1 Read limit positions MIN 15 00 MAX 850 25 SOH Adr Cmd EOT CRC Transmission 01h 20h 67h 04h 42h SOH Adr Cmd MIN limit position 0015 00 MAX limit position 0850 25 EOT CRC Response 01h 20h 67h 30h 30h 31h 35h 30h 30h 30h 38h 35h 30h 32h 35h 04h 1Fh Example 2 Write limit positions MIN 33 22 MAX 1234 56 SOH Adr Cmd MIN limit position 033 22 MAX limit position 1234 56 EOT CRC Transmission 01h 20h 67...

Page 20: ...Data EOT CRC Transmission 01h 83h 69h 30h 04h CDh Response not confirmed Important Parameters are programmed in mm and auto converted by SPA into inches upon displaying the po sition values 4 3 8 Read write timeout at bus error RS485 j 6Ah This command is utilized to read or write the system time timeout at bus error Value range is within 00 1 s to 99 9 s Tolerance 7 at minimum time 1 at maximum t...

Page 21: ...ters to adapt them to new circumstances Presently the following sub parameter is available D 44h delaytime for minimized timeout reply of serial interface Sub Parameter Delaytime D 44h This parameter defines the minimum delay time break between the last bit received and the first bit of the re sponse transmitted Delay time is programmable in steps of 0 1 ms from 00 0 60 0 ms default is 1 0 ms Exam...

Page 22: ...oadcast command address Identifier 99 will make every networked SPA indicate the device specific identifier in the bottom line of the display The upper line is blind This command is a designated broadcast command SOH Adr Cmd EOT CRC Transmission 01h 83h 41h 04h 80h Response Not confirmed SPA remains in this mode until being switched off and on again or until transmission of another command ex cept...

Page 23: ...he SPA display now is indicating 5 hyphens instead of target 4 5 2 SPA restore default Q 51h This command restores default either of individual or collective parameters Data q 71h Restore default parameters Data t 74h Device identifier 98 Data x 78h Multiturn counter reset to 0 No singleturn reset possible Data 7Fh All above functions are accomplished Note No profile reset Profile reset by command...

Page 24: ...erial number 07090EA4 EOT CRC Response 01h 20h 58h 53h 30h 37h 30h 39h 30h 3Eh 3Ah 34h 04h 20h Code configuration of the transmitted serial number The Low Nibble lower 4 bits of a byte of the 8 data bits received equal together a 4 byte value comprising the serial number The serial number is composed by date and time of production Since also the seconds are coded and by as signing only one number ...

Page 25: ...nt value usually target MAX limit of SPA hurt by manual positioning operation utilizing key Troubleshooting Set SPA to the admissible positioning range MIN limit of SPA hurt by manual positioning operation utilizing key Troubleshooting Set SPA to the admissible positioning range SPA did not reach target window Troubleshooting Extend the tolerance window Set switchover to precision speed at an earl...

Page 26: ...nch j 69h 3 X X X X Parameter timeout bus error k 6Bh 9 X X X Parameter motor system times m 6Dh 5 X X X Read write general parameters t 74h 6 X Transmit tool number u 75h 6 X Transmit optional column of figures x 78h 5 X X X Read write specific parameters A 41h 2 X X X X Assign or display device identifier B 42h 2 SPA response in addressing mode C 43h 3 X Check if current value target D 44h 1 X X...

Page 27: ... Motive positioning Two softkeys with jog operation for format alignment connected to power tool by infrared interface Standard DIN EN 61010 1 Protection class II Overvoltage category II Pollution degree 2 Interference emission DIN EN 61000 6 3 Interference immunity DIN EN 61000 6 2 Approval UL cUL Technical data mechanical design Hollow shaft ø14 mm Operating speed 600 rpm short term Protection D...

Page 28: ...5 22 16 13 37 6 5 45 14 30 15 31 8 26 12 5 ø14H7 ø20 1 75 28 4 8 6 ø6h9 0 5x 45 2 1 Pin M4 Connector Female connector Torque pin Seal Status LED IR Diode 8 Part number Reference Interface 1 RS485 E connection 0 Connector output 1 Cable output 4 pin M8 connector Supply voltage 3 24 VDC Display A At slope Hollow shaft A ø14 mm N 153 1 3 A A01 ...

Reviews: