BE1-50/51B-217 General Information
1-3
Load Demand Curve
Scenario
Configure the relay such that when the sensed current is:
1.05 times pickup
Time to trip
1.0 hour
1.2 times pickup
Time to trip
1.0 hour
1.5 times pickup
Time to trip
2.0 minutes
4.0 times pickup
Time to trip
0.2 seconds
6.0 times pickup
Time to trip
0.2 seconds
Settings
Position the following switches as designated. (Switch locations are shown in Section 2,
Controls And
Indicators.) Figure 1-2 is a graph showing the timing for the application scenario.
SW8-1
Select nominal operating frequency
SW8-2
OFF (open) no instantaneous delay
SW8-3
OFF (open) no instantaneous delay
SW8-4
ON (closed) integrating reset selected
TIME DIAL
4.0
CURVE
S
TIME PICKUP
Select preferred time pickup level
INST PICKUP
Select preferred instantaneous pickup level
SPECIFICATIONS
BE1-50/51B-217 Overcurrent Relay has the following features and capabilities.
Current Sensing Input
Continuous current: 14 amperes. One second current: 400 amperes.
TIME PICKUP Range
0.5 to 15.9 amperes in 0.1 ampere steps. Setting the TIME PICKUP to
the minimum pickup (0.5 ampere), places the relay in the most sensitive
state and may be used as a safety setting.
TIME Dropout
Dropout occurs at 95% of pickup value.
TIME PICKUP
Accuracy
±2% ±25 milliamperes at or above 0.5 ampere settings.
Frequency Response
A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
TIME DIAL Range
0.0 to 9.9, in 0.1 steps.
INST PICKUP Range
1 to 99 amperes in 1 ampere steps. Setting the INST PICKUP to the
minimum pickup (1.0), places the relay in the most sensitive state and
may be used as a safety setting.
INST Dropout
Dropout occurs at 95% of pickup value.
Summary of Contents for BE1-50/51B-217
Page 26: ...BE1 50 51B 217 Controls and Indicators 2 3 Figure 2 2 Location of Controls and Indicators...
Page 29: ...BE1 50 51B 217 Functional Description 3 3 Figure 3 1 Functional Block Diagram...
Page 31: ...BE1 50 51B 217 Installation 4 2 Figure 4 1 Panel Drilling Diagram S1 Case Semi Flush Mount...
Page 33: ...BE1 50 51B 217 Installation 4 4 Figure 4 3 Panel Drilling Diagram S1 Case Projection Mount...
Page 37: ...BE1 50 51B 217 Installation 4 8...
Page 40: ...BE1 50 51B 217 Installation 4 11 Figure 4 7 BE1 50 51B 217 Overcurrent Relay Rear View...