BE1-50/51B-217 General Information
1-6
Harmonic Response
BE1-50/51B harmonic rejection is illustrated in Figure 1-4.
Figure 1-4 shows that a relay set for one ampere pickup would pickup at
0.96 ampere on a current containing 40% seventh harmonic. This
corresponds to a ten-to-one rejection ratio. Other conditions may be
evaluated in the same manner.
Figure 1-4. Harmonic Response
INST Characteristics
BE1-50/51B instantaneous characteristic curves are similar to standard
electromechanical instantaneous units. However, the time to trip for
ground applications is slightly longer than that for phase applications to
allow time to power-up the relay. Longer trip time for ground
applications is beneficial because it helps to avoid nuisance trips.
For phase applications, the maximum time to trip is 3.5 cycles at a
pickup multiple of 1.0, and 1.5 cycles at a pickup multiple of 3.0. The
corresponding times for ground applications are 4.5 and 1.75 cycles.
Figure 1-5 shows the instantaneous characteristic curves for maximum
time to trip.
Additional delays of 0.1, 0.2, or 0.3 seconds may be added with internal
switches SW8-2 and -3. These delays apply to both phase and ground
applications. Closing switch SW8-2 provides an additional delay of 0.1
second. Closing switch SW8-3 provides an additional delay of 0.2
second. Closing both switches SW8-2 and -3 provides an additional
delay of 0.3 second. Section 2 illustrates the location of SW8.
Summary of Contents for BE1-50/51B-217
Page 26: ...BE1 50 51B 217 Controls and Indicators 2 3 Figure 2 2 Location of Controls and Indicators...
Page 29: ...BE1 50 51B 217 Functional Description 3 3 Figure 3 1 Functional Block Diagram...
Page 31: ...BE1 50 51B 217 Installation 4 2 Figure 4 1 Panel Drilling Diagram S1 Case Semi Flush Mount...
Page 33: ...BE1 50 51B 217 Installation 4 4 Figure 4 3 Panel Drilling Diagram S1 Case Projection Mount...
Page 37: ...BE1 50 51B 217 Installation 4 8...
Page 40: ...BE1 50 51B 217 Installation 4 11 Figure 4 7 BE1 50 51B 217 Overcurrent Relay Rear View...