background image

3-1

SECTION 3

FUNCTIONAL DESCRIPTION

GENERAL

BE1-50/51B-217 Overcurrent Relays are microprocessor based non-directional relays that measure ac
current to provide secure and reliable instantaneous and time overcurrent protection for power systems.

FUNCTIONAL DESCRIPTION

Sensing Input

Single phase ac current from system current transformers (CT) is brought into the BE1-50/51B
Overcurrent Relay at terminals eight and nine.  Refer to Figure 3-1 to follow the functional description. 
The input current is applied to internal power and signal CTs.

Power Supply

Current from the power CT is rectified, filtered, and supplied to all of the internal circuitry for operating
power.  A pre5 Vdc supply also serves as a reference for automatic calibration.

Instantaneous Signal

Current from the signal CT is rectified and applied to the instantaneous scaling resistors controlled by
the INST PICKUP selector switches.  The analog voltage of the instantaneous input signal developed
across the scaling resistors is filtered and applied to the multiplexor (MUX).

Time Signal

Current from the signal CT is also rectified and applied to the time scaling resistors controlled by the
TIME PICKUP selector switches.  The analog voltage of the time input signal is also filtered and applied
to the multiplexor.

Microprocessor

Operating power from the power supply is applied to the microprocessor supervisor circuit.  When the
input current falls below an acceptable level, the supervisor circuit interrupts the microprocessor and
halts further operation.  A microprocessor watchdog feature resets the microprocessor program when
the program flow is interrupted.

Information from the TIME DIAL selector switches, the TIME CURVE selector switch, and the 50/60 Hz,
INST DELAY, and RESET CHAR switches is also applied to the microprocessor.  The microprocessor
uses these inputs to set the operating parameters.

When the microprocessor is ready for analog information from the multiplexor, microprocessor control
signals cause the multiplexor to route the desired input through to the output.  The output is converted
from an analog value to a digital value and applied to the microprocessor.

Summary of Contents for BE1-50/51B-217

Page 1: ...r Electric R PICKUP PICKUP 0 5 MIN SET TIME DIAL TENTHS UNITS TENTHS UNITS CURVE INST TIME MANUAL TRIP MANUAL TRIP UNITS TENS INST TIME SOLID STATE PROTECTIVE RELAY D2718 16 vsd 12 14 99 INSTRUCTION M...

Page 2: ...m the procedures presented in this manual INTRODUCTION This manual provides information concerning the operation and installation of the BE1 50 51B 217 Overcurrent Relay To accomplish this the followi...

Page 3: ...Basler Electric Co Highland IL 62249 December 1999 It is not the intention of this manual to cover all details and variations in equipment nor does this manual provide data for every possible continge...

Page 4: ...st 4 1 Mounting 4 1 Panel Drilling Diagram S1 Case Semi Flush Mount 4 2 Outline Dimensions For S1 Case Semi Flush Mount 4 3 Panel Drilling Diagram S1 Case Projection Mount 4 3 Outline Dimensions BE1 5...

Page 5: ...iv CONTENTS Continued SECTION 6 MAINTENANCE 6 1 General 6 1 In House Repair 6 1 Storage 6 1 Periodic Tests 6 1 General 6 1 Periodic Test 6 2 SECTION 7 MANUAL CHANGE INFORMATION 7 1...

Page 6: ...e method to manually trip the breaker at the relay front panel Direct reading front panel controls Minimum pickup setting for safety during installation Time characteristics extend to a pickup multipl...

Page 7: ...1 50 51B 217 OVERCURRENT RELAY R Basler Electric Highland Illinois PICKUP PICKUP PICKUP ME DIAL TENTHS UNITS TENTHS S CURVE INST TIME TEST TR ST TRIP U TENS INST TIME 0 0 S 0 0 12 14 99 D2718 17 vsd F...

Page 8: ...CKUP Select preferred instantaneous pickup level SPECIFICATIONS BE1 50 51B 217 Overcurrent Relay has the following features and capabilities Current Sensing Input Continuous current 14 amperes One sec...

Page 9: ...eral Information 1 4 0 01 0 1 1 10 100 1000 10000 1 10 40 Instantaneous Tap 5 amps Time Tap 1amp Curve S Time Dial 4 0 1 2 3 4 5 MULTIPLE OF PICKUP T I M E I N S E C O N D S Figure 1 2 Load Demand Cha...

Page 10: ...the nominal 50 60 hertz current causes less than 0 5 change in the current required for pickup INST Transient Response Less than 10 overreach with system time constants up to 40 milliseconds Burden B...

Page 11: ...llow time to power up the relay Longer trip time for ground applications is beneficial because it helps to avoid nuisance trips For phase applications the maximum time to trip is 3 5 cycles at a picku...

Page 12: ...t characteristic prevents the ratcheting effect that may occur with repeating system faults Closing SW8 4 selects the integrating reset characteristic The integrating reset characteristic simulates th...

Page 13: ...30 amperes for 0 2 seconds carry 7 amperes for 2 125 250 Vdc minutes 3 amperes continuously and break 0 3 ampere 0 3 amperes L R 0 04 This chart vertical axis x D Seconds is applicable for all curves...

Page 14: ...a five watt hand held transceiver operating at random Interference RFI frequencies centered around 144 megahertz and 440 megahertz with the antenna located six inches from the relay in both horizonta...

Page 15: ...BE1 50 51B 217 General Information 1 10 MULTIPLES OF PICK UP Figure 1 7 Time Characteristic Curve 99 1610 Load Demand Curve...

Page 16: ...BE1 50 51B 217 General Information 1 11 MULTIPLES OF PICK UP Figure 1 8 Time Characteristic Curve 99 1370 L Long Inverse...

Page 17: ...BE1 50 51B 217 General Information 1 12 MULTIPLES OF PICK UP Figure 1 9 Time Characteristic Curve 99 1371 D Definite Time...

Page 18: ...BE1 50 51B 217 General Information 1 13 MULTIPLES OF PICK UP Figure 1 10 Time Characteristic Curve 99 1372 M Moderately Inverse...

Page 19: ...BE1 50 51B 217 General Information 1 14 MULTIPLES OF PICK UP Figure 1 11 Time Characteristic Curve I Inverse...

Page 20: ...BE1 50 51B 217 General Information 1 15 MULTIPLES OF PICK UP Figure 1 12 Time Characteristic Curve 99 1374 V Very Inverse...

Page 21: ...BE1 50 51B 217 General Information 1 16 MULTIPLES OF PICK UP Figure 1 13 Time Characteristic Curve 99 1375 E Extremely Inverse...

Page 22: ...BE1 50 51B 217 General Information 1 17 MULTIPLES OF PICK UP Figure 1 14 Time Characteristic Curve B 99 1376 BS142 B...

Page 23: ...BE1 50 51B 217 General Information 1 18 MULTIPLES OF PICK UP Figure 1 15 Time Characteristic Curve 99 1377 BS142 C...

Page 24: ...ripping E CURVE Selector Ten position selector switch to select one of nine inverse functions or one fixed time function F TIME DIAL Selectors Two selector switches TENS and UNITS to select the desire...

Page 25: ...des integrating reset Opening SW8 4 provides instantaneous reset K Auxiliary Output Jumper Terminations Configures the auxiliary output contacts to close with either the instantaneous 50 trip and or t...

Page 26: ...BE1 50 51B 217 Controls and Indicators 2 3 Figure 2 2 Location of Controls and Indicators...

Page 27: ...s the scaling resistors is filtered and applied to the multiplexor MUX Time Signal Current from the signal CT is also rectified and applied to the time scaling resistors controlled by the TIME PICKUP...

Page 28: ...are closed in accordance with the time characteristic curve If the sensed current exceeds the INST PICKUP setting the INST contacts 50 are closed Power Off Sensing The power off sensing circuits meas...

Page 29: ...BE1 50 51B 217 Functional Description 3 3 Figure 3 1 Functional Block Diagram...

Page 30: ...peration of the relay may be confirmed by performing the operational test procedure Page 4 6 In the event the relay is not to be installed immediately store the relay in its original shipping carton i...

Page 31: ...BE1 50 51B 217 Installation 4 2 Figure 4 1 Panel Drilling Diagram S1 Case Semi Flush Mount...

Page 32: ...0 51B 217 Installation 4 3 D2750 24 vsd 12 17 99 NUMBERS IN PARENTHESES INDICATE METRIC DIMENSIONS MILLIMETERS ALL OTHER DIMENSIONS ARE IN INCHES Figure 4 2 Outline Dimensions For S1 Case Semi Flush M...

Page 33: ...BE1 50 51B 217 Installation 4 4 Figure 4 3 Panel Drilling Diagram S1 Case Projection Mount...

Page 34: ...EXTENSION TYP FOR DETAILED INSTRUCTIONS SEE THE TERMINAL PROJECTION MOUNTING KIT SUPPLIED MOUNTING PANEL 62 48 2 195 55 75 49 53 1 95 2 40 DETAIL A A SHOWING THE ADDITION OF WASHERS OVER THE BOSS TO...

Page 35: ...BE1 50 51B 217 Installation 4 6 Figure 4 4 Outline Dimensions BE1 50 51B S1 Case Projection Mount...

Page 36: ...eck model and part number before connecting and energizing a particular relay Connections should be made with minimum wire size of 14 AWG except as noted for the ground wire Typical ac input and dc co...

Page 37: ...BE1 50 51B 217 Installation 4 8...

Page 38: ...BE1 50 51B 217 Installation 4 9 Figure 4 6 DC Control Connections And Jumper Configuration Terminals...

Page 39: ...BE1 50 51B 217 Installation 4 10 9 8 10 7 5 3 1 6 4 2 CT GND 51 50 AUX D1146 16 04 23 96 OVERCURRENT...

Page 40: ...BE1 50 51B 217 Installation 4 11 Figure 4 7 BE1 50 51B 217 Overcurrent Relay Rear View...

Page 41: ...nal test procedures in this Section In the event the relay is not to be installed immediately store the relay in its original shipping carton in a moisture and dust free environment DIELECTRIC TEST In...

Page 42: ...E1 50 51B 9 8 7 6 5 4 2 TIME INST 3 CURRENT SOURCE INPUT STOP TIMER START AMPS TEST SET 12 17 99 D2750 26 vsd 1 0Aac CURRENT LIMITER TARGET CURRENT Figure 5 1 Pickup and Timing Test Setup Figure 5 2 T...

Page 43: ...put current of 0 550 ampere Step 2 Decrease input current until PICKUP LED turns OFF Step 3 Set TIME PICKUP to 2 2 Step 4 Slowly increase current to terminals 8 and 9 PICKUP LED should turn ON at an i...

Page 44: ...from when current is applied until TIME output contacts close Step 2 Apply the current step from 0 to 1 5 amperes and record the elapsed time Elapsed time should be 72 49 to 99 38 seconds This toleran...

Page 45: ...MANUAL TRIP test points Check that TIME target operates Step 4 Connect a jumper between INST MANUAL TRIP test points Check that INST target operates Step 5 Reset targets Integrating Reset Test Perfor...

Page 46: ...riodic testing should consist of the following procedures Step 1 Verify that the instantaneous pickup is within 2 of the value set on the dials Pickup occurs when the INST output contacts close Step 2...

Page 47: ...ement parts must be at least equal to that of the original components Where special components are involved Basler Electric part numbers may be obtained from the number stamped on the component or ass...

Page 48: ...curs when the LED turns ON Step 3 Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as the time given on the characteristic curve Refer to Section 1 fo...

Page 49: ...tantive changes to date are summarized in the Table 7 1 Table 7 1 Changes Revision Summary of Changes ECO Date A Deleted all references to the service manual corrected Figures 3 1 and 5 2 and changed...

Reviews: