background image

LV-8RCL

Low Voltage Power Distribution Module

The LV-8RCL distributes power from a low voltage power source to 8 fused outputs 

through 8 Output Isolation Relay sockets. Terminals are provided for control of each 

output relay by an Access Control system. Output devices can be powered separately 

from the control relays by configuring Common Power Jumpers. A 2-pole Disconnect 

Relay socket is provided and easily interfaces with Fire, Life Safety or Alarm Panels to 

provide Emergency Power Disconnect. Relay auxilary contact terminals are provided 

for alarm monitoring of the Disconnect feature.

Each model includes jumpers configurable for 3 modes of operation:

 

1) 8 outputs that are disconnected by the Disconnect Relay

 

2) 8 outputs that are unaffected by the Disconnect Relay

 

3) 4 x 4 mode (Outputs 1-4 = Mode 1, Outputs 5-8 = Mode 2)

The LV-8RCL includes red LED indicators at each of the 9 relay positions for iden-

tification of energized relays.

The module is 5.00” wide x 8.00” long. The installed height with relays is 2.50”. 

Standoffs are included for mounting the circuit board in a user-supplied enclosure.  

Relays and 3AG-type Fuses are provided separately.  To meet UL Listing require

-

ments, the relays selected should be Idec Corp., P/N RH1B-U SPDT or P/N RH2B-U, 

DPDT, 12vdc or 24vdc.

* * *  WARNING  * * *

Turn off all power feeding the module terminals before servicing or changing input/output wiring, removing 

or reinstalling fuses or relays, or cutting jumpers.  Failure to observe this warning may cause electrical shock 

hazard or may damage internal or external circuit components.

The information in this manual is believed to be accurate in all respects. However, BASE Electronics cannot assume 

responsibility for any consequences resulting from the use thereof. The information contained herein is

subject to change and BASE Electronics may issue a revision to incorporate such changes at any time.

 

INSTALLATION

Locate the unit inside a NEMA 1 enclosure (such as a BASE LVPC Low Voltage Power 

Cabinet) close to the source power supply.  Drill (4) 0.187” diameter holes to match 

the (4) corner holes in the printed circuit board.  Push the nylon standoffs supplied 

into each hole and snap the module into place.

POWER SUPPLY WIRING

Common Relay Control and Output Voltage  If the output devices require a DC 

operating voltage, the Common Power Jumpers can remain intact and only one DC 

power supply needs to be connected to the PWR input terminals. In this mode, the 

DC operating voltage of the control relays, output devices and the power supply must 

match. Example: Output devices = 24VDC Maglocks, Power Supply = 24VDC, 

Relays must be 24VDC.

Separate Relay Control and Output Voltage

By cutting the Common Power Jumpers, two separate power supplies of like or dif-

ferent voltages can be used to power the output devices (use the PWR terminals) and 

control relays (use the CTL terminals). The CTL power supply must be DC while the 

PWR power supply can be either AC or DC.

Connect the power supply input leads to the terminal strip at the lower left side of the 

module as shown in Figure 1. Use a minimum of 18AWG copper conductors for this 

wiring and keep the length to the power supply as short as possible.

MODE CONFIGURATION

Each module includes 8D and 4X4 jumpers for configuring the mode of operation.

Continuous Power Mode

  When no jumpers are cut, the outputs are continuously 

powered and unaffected by the Disconnect feature. If Emergency Power Disconnect 

is not needed, do not cut any jumpers and do not install a 2-pole relay at the Discon-

nect Relay socket.

8 Disconnect Mode

  When the 8D jumper is cut, all 8 outputs will be disconnected 

by the Disconnect Relay when the Fire Panel Interface control circuit is opened. A 

2-pole Disconnect Relay must be installed in the socket provided.

4 X 4 Mode

  When the 4 X 4 Jumper is cut, outputs 1-4 will operate in the Disconnect 

mode and outputs 5-8 will be unaffected by the Disconnect feature. A 2-pole Discon

-

nect Relay must be installed in the socket provided.

POWER DISCONNECT WIRING

A socket is provided for a 2-pole relay that is used to disconnect the output power PWR 

during facility emergencies. The relay is DC powered from the power feeding the CTL 

terminals. Normally closed dry contacts of a fire or life safety system panel are used to 

control the disconnect relay at the ‘F’ terminals. The alarm contact should be rated for 

the current required by the relay selected (normally less than 50mA at 12VDC).

The auxiliary output contacts of the Disconnect Relay can be monitored. Note that the 

terminals designated NO and NC (shown in Figure 1) stand for Normally Open and 

Normally Closed when the relay is de-energized. The terminal marked ST is a Spare 

Terminal available for termination of an end-of-line resistor if needed.

OUTPUTS AND CONTROLS

Add the operating current ratings for each device to be powered from one output to 

determine the expected operating current flow. Install a fuse for the output that will 

trip when this value is exceeded. The value of the fuse selected for each output may 

be written on the white area below the fuse for easy future reference.

Example A:

  Output 1 - (1) magnetic lock

 

operating current = 0.29A at 12 VDC

 

Install fuse rated just greater than 0.29A = 3/8A or 1/2A

Example B:

  Output 2 - (4) deadbolt locks

 

operating current = (4 x 0.40A) = 1.6A 

 

Install fuse rated just greater than 1.6A = 2A

Add the operating current ratings for each control relay and install a control fuse that 

will trip when this value is exceeded. The value of the fuse selected may be written 

on the white area below the fuse for easy future reference.

When powering devices over considerable distances, the cabling resistance may be 

so high that the voltage available at the device drops to an unacceptable level.  To 

prevent this from occuring, the system cabling should be designed with adequate sized 

conductors.Use the Low Voltage System Cabling Design Guide in this manual for help 

in obtaining the desired results. Wiring to output devices connects to the OUTPUTS 

terminals. Three terminals are provided for each output. ‘NC’ or ‘NO’ designates the 

fused output terminal. ‘Com’ designates the voltage Common terminal. Suggested 

wiring methods for OUTPUTS and CONTROLS are shown in Figure 1.

LIGHTNING, TRANSIENT AND NOISE SUPPRESSION

Lightning or transient suppression devices may be installed at the LV-8A output terminals to protect control equip-

ment from induced voltages.  A multi-screw, solid ground bar should be installed vertically next to the output side 

of the module for connection of metal oxide varistors, transient suppression diodes, etc. If shielded cable is used 

for output wiring, shield drain wires can be connected to the ground bar for line noise suppression. Run a minimum 

#14AWG green stranded ground wire from the ground bar to the closest Service Ground. Grounding bars of the 
type mentioned above can be separately supplied by BASE Electronics.

LOW VOLTAGE SYSTEM CABLING DESIGN GUIDE

With an improperly designed cabling system, the resistance of wire conductors may cause a voltage drop that 

could significantly affect the performance of the powered device. The resistance of a given length of cabling and 

its voltage drop at the given operating voltage can be calculated. This allows the affect on the powered device to 

be estimated with adjustments in conductor size implemented in the design stage.

Example:

A CCTV camera requires 0.29A at 24 VAC and the estimated cable length from the power supply is 800 feet.  

The camera specifications state that the camera will operate properly down to 21.0 VAC (a voltage drop of 3.0 

volts maximum).  What should be the size of the power cable conductors? From the chart below, we observe that 

a pair of 18AWG stranded copper conductors will have a resistance of 2 x 800 feet x 6.48 ohms/1000 feet. Using 

Ohm’s Law: E = I x R

E (voltage dropped) = I (the required current) x R (the cabling resistance)

 

E = (0.29) x (2 x 800 x (6.48/1000)) = 3.007 volts

Subtracting 3.007 volts from 24VAC leaves 20.993 volts available at the camera, an unacceptable level. When 

16AWG conductors are used in the equation: E = (0.29) x (2 x 800 x (3.67/1000)) = 1.703 volts

Subtracting 1.703VAC from 24VAC  leaves 22.297VAC available at the camera. Taking future expansion of a second 

camera into account, the estimator may decide to increase the conductors to #14AWG as follows:

E = (2 x 0.29) x (2 x 800 x (2.31/1000)) = 2.14VAC dropped

When powering inductive devices (relay coils, electric strikes, magnetic locks, etc.), remember to install reversing 

diodes (DC powered) or metal oxide varistors (AC powered) at the device terminals or as recommended by the 

device manufacturer to counter the affect of Counter Magnetic Force (CMF).

Resistance of Copper Conductors

 

Solid Conductors 

Stranded Conductors

 

Wire Gage 

Resistance 

Wire Gage 

Stranding 

Resistance

 

(AWG) 

(Ω/1000’) 

(AWG) 

(#/AWG) 

(Ω/1000’)

 

10 

1.00 

10 

37/26 

1.11

 

12 1.59 12 7/20 1.45

 

14 

2.53 

14 

7/22 

2.31

 

16 

4.02 

16 

7/24 

3.67

 

18 

6.39 

18 

16/30 

6.48

 

20 

10.15 

20 

10/30 

10.32

 

22 

16.14 

22 

7/30 

14.74

 

24 

25.67 

24 

7/32 

23.30

Reviews: